Using the Fire Control Instruments 7100 Aux. Power Output
The 7100’s 24 VDC non-resettable auxiliary power circuit is compatible with the S/FDACT. Connect
S/FDACT terminal 15 (+24) to the 7100 BSM terminal TB4-2 (+), and connect S/FDACT terminal 16 (C)
to the BSM terminal TB4-3 (-).
Using the Fire Control Instruments 7200 Aux. Power Output
The 7200’s 24 VDC non-resettable auxiliary power circuit is compatible with the S/FDACT. Connect
S/FDACT terminal 15 (+24) to the 7200 PSU/SPSU terminal TB1-1 or TB1-2 (+), and connect S/FDACT
terminal 16 (C) to the PSU/SPSU terminal TB1-3 or TB1-4 (-).
Using the Edwards System Technology EST2 Aux. Power Output
The EST2’s 24 VDC non-resettable auxiliary power circuit is compatible with the S/FDACT. Connect
S/FDACT terminal 15 (+24) to the EST2 PPS terminal TB3 SMK/AUX PWR (+), and connect S/FDACT
terminal 16 (C) to the PPS terminal TB3 SMK/AUX PWR (-). Install PPS jumper JP4 to set the AUX
PWR output to non-resettable.
Using the Mirtone MIR2 Aux. Power Output
The MIR2’s 24 VDC non-resettable auxiliary power circuit is compatible with the S/FDACT. Connect
S/FDACT terminal 15 (+24) to the MIR2 PPS terminal TB3 SMK/AUX PWR (+), and connect S/FDACT
terminal 16 (C) to the PPS terminal TB3 SMK/AUX PWR (-). Install PPS jumper JP4 to set the AUX
PWR output to non-resettable.