SAFETY PRECAUTIONS

THIS SYMBOL WARNS YOU THAT SERIOUS BURNS 
OR OTHER INJURIES MAY RESULT IF SAFETY IN-
STRUCTIONS ARE NOT FOLLOWED.

• This service manual should be retained in a safe
   place for future reference. The installation of your 
   new fryer must conform to local codes or in the 
   absence of local codes, with the current National 
   Fuel Gas Code ANSI Z223.1/NFPA 54 (latest
   edition), Natural Gas Installation Code  
   CAN/CGA-B149.1 or Propane Installation Code 
   CAN/CGA-B149.2.

• Your ventilation hood, when installed, must         
   conform to the current ANSI/NFPA 96 standard
   (latest edition).

• No frame or restriction shall be constructed 
   around the fryer that will restrict air movement 
   into the fryer’s combustion area or prevent proper
   ventilation.

• Keating fryers are designed to operate on the 
   gas fuel specified on the serial plate and must 
   not be operated with another gas fuel. They 
   cannot be converted to another gas fuel by 
   turning or engaging a switch.

DO NOT STORE OR USE GASOLINE OR OTHER FLAM-
MABLE VAPORS AND LIQUIDS IN THE VICINITY OF 
THIS OR ANY APPLIANCE.

You will post, in a prominent location, instructions to 
be followed in the event the user smells gas. This
information shall be obtained from your local gas
supplier.

IMPORTANT: IN THE EVENT A GAS ODOR IS DE-
TECTED, SHUT DOWN UNIT AT MAIN SHUT-OFF 
VALVE AND CONTACT THE LOCAL GAS COMPANY 
OR GAS SUPPLIER FOR EMERGENCY SERVICE.

• You must maintain this appliance free and clear 
   from combustibles. 

• You must maintain the following minimum 
   clearances from combustible and  
   non-combustible construction:   

MINIMUM CLEARANCE

CONSTRUCTION CLEARANCES

COMBUSTIBLE

NON-COMBUSTIBLE

BACK

6"

0"

RIGHT SIDE

6"

0"

LEFT SIDE

6"

0"

SUITABLE FOR NON– COMBUSTIBLE FLOORS

The Keating Gas Fryer must be installed in an area 
providing adequate air supply and ventilation. Do not 
obstruct the fl ow of combustion and ventilation air. 
Proper ventilation is one of the important consider-
ations for effi cient operation of the Keating Gas Fryer. 
It should be installed so that the products of combus-
tion are removed effi ciently without producing drafts 
that will interfere with proper burner operation. The 
intake for the exhaust fan should not be placed close 
to the fl ue of the Keating Gas Fryer to insure proper 
air fl ow necessary for combustion. The area around 
the front and bottom of the Keating Gas Fryer must 
be kept clear and unobstructed. In the USA the ven-
tilation systems must conform to the ANSI/NFPA96 
latest edition. “A minimum of 18" (457mm) should 
be maintained between the fl ue outlet and the lower 
edge of the grease fi lters.” Must be installed at least 
16" away from any open fl ame. It is the responsibil-
ity of the owner and the local installer to comply with 
national and local codes.

FIRST STEPS

NATIONAL CODE REQUIREMENT

The installation must conform with local codes, or 
in the absence of local codes, with the National 
Fuel Gas code, ANSI Z223.1 or the Natural gas 
Installation Code, CAN/CGA-B149.1 or the Propane 
Installation Code, CAN/CGA-B149.2. Flexible connec-
tors must comply to ANSI Z221.69/CAN/CGA1.16.

When pressure testing at test pressures less than or 
equal to 1/2 psig (3.45 KPA), fryer 

must be isolated

 

from gas supply piping. When pressure testing at test 
pressures above 1/2 psig (3.45 KPA), fryer 

must be 

disconnected

 from gas supply piping system.

POSITIONING

The fryer must be no closer than 6 inches from 
any combustible material and 16 inches away from 
any open fl ame. The fryer must be placed under 
an exhaust hood with a fi re retardant system. Your 
ventilation hood, when installed, must conform to the 
current ANSI/NFPA 96 standard. ALL connections 
and placement must comply with local and national 
codes. It is the responsibility of the owner and local 
installer to comply with these regulations when in-
stalling the fryer.

Counter model and fl oor model fryers must be 
restrained to prevent tipping when installed in order 
to avoid splashing, spilling, etc. of hot liquid. The 
restraining method may be a manner of installation or 
by separate means.

Содержание Instant Recovery 2000 Series

Страница 1: ......

Страница 2: ...ACTURER S INSTRUCTIONS THIS PRODUCT COULD EXPOSE YOU TO SUBSTANCES IN FUEL OR IN FUEL COMBUSTION WHICH CAN CAUSE DEATH OR SERIOUS ILLNESS AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER...

Страница 3: ...tions of any kind to your equipment will void the warranty Before uncrating check equipment carefully for damage IF EQUIPMENT ARRIVES DAMAGED Keating does not assume responsibility for loss or damage...

Страница 4: ...portant consider ations for efficient operation of the Keating Gas Fryer It should be installed so that the products of combus tion are removed efficiently without producing drafts that will interfere...

Страница 5: ...STERS IT MUST BE INSTALLED WITH CASTERS SUPPLIED A CONNECTOR COMPLYING WITH EITHER ANSI Z21 69 OR CAN CGA 6 16 AND A QUICK DIS CONNECT DEVICE COMPLYING WITH EITHER ANSI Z21 41 OR CSA 6 9 IT MUST ALSO...

Страница 6: ...leave your fryer operating unattended When all previous instructions have been completed Check the serial plate on the panel inside cabinet to determine if the burner is set up for the proper type gas...

Страница 7: ...E SWITCHING THE FRYER ON IF OIL LEVEL DROPS BELOW TOP OF HEAT TRANSFER TUBES SEVERE DAMAGE TO FRYER AND INJURY TO OPERATOR MAY RESULT WATER IN ANY FORM AND HOT OIL DON T MIX OIL EXPANDS WHEN HEATED TH...

Страница 8: ...he OFF position 2 Turn MAIN POWER switch to the OFF position 3 Turn gas valve knob to the OFF position 4 Turn gas supply valve to the OFF position 5 Check to make sure all burners and pilot are out BB...

Страница 9: ...designed to provide maximum production efficiency and deliver high quality food products Low temperature cooking highly polished stainless steel and a true COLD ZONE mean extended oil life Follow the...

Страница 10: ...show StO for ap proximately two seconds and the timer will return to normal operation Repeat the process as necessary for the other timers OPERATING LOGIC When the timer is powered up the display will...

Страница 11: ...CLE CLEANING AND BOIL OUT FOR A SINGLE FRYER When cleaning and boiling out your fryer use Keating Sea Powder and Keating Klenzer to keep your fryer in top condition Keating Sea Powder dissolves any gr...

Страница 12: ...ETTING MOTOR TO PREVENT SERIOUS INJURY WHEN RESET SWITCH IS ENGAGED SEE FILTER MANUAL 16 Check thermostat bulb positioning see page 12 17 Refill the fryer with new or filtered oil FOR A FRYER WITH ATT...

Страница 13: ...d damaging the fryer do not power wash spray or hose it down while cleaning it 17 Pump must be primed with oil after boil out with water FAILURE TO LUBRICATE PUMP MAY CAUSE SEVERE DAMAGE TO FILTER SYS...

Страница 14: ...meter in same position for every calibration 4 If calibration of fryer is found to be less than 25 F off simply loosen four dial plate retaining screws rotate dial plate to match thermometer reading a...

Страница 15: ...pression fitting snugly into fryer vessel 5 Adjust bulb so at least 2 of bent portion of it is next to heat transfer tube and tighten compression nut onto compression fitting for fryer 10x11 18 up The...

Страница 16: ...uct overloaded in fryer vessel c Oil is breaking down and foaming d Water in cold zone a Fill fryer up to Fill Level line as oil expands when heated b Follow recommended cooking production figures in...

Страница 17: ...plates are damaged or lost replace them immediately B C A D E BACK PANEL F PARTS LIST GAS FRYER CONTROL PANEL AA GAS ITEM QTY DESCRIPTION P N A 1 THERMOSTAT DIAL PLATE 375 058037 B 1 THERMOSTAT KNOB...

Страница 18: ...CKER WHITE MOMENTARY 032297 Push to Light Hi Limit Test G 1 SWITCH MELT IDLE FRY 032829 H 1 INDICATING LIGHT GREEN 021255 I 1 INDICATING LIGHT RED 021209 J 1 HIGH LIMIT Resettable 034357 K 1 FLAME SWI...

Страница 19: ...016341 E 1 RUNNER PILOT TUBE ASSEMBLY 019408 F 1 GAS VALVE NATURAL 023625 LP 023624 POT ASSEMBLY 14AA GAS F A B C D E ITEM QTY DESCRIPTION P N A 3 3 FIN RADIANT 000041 B 1 POT WELDMENT 14 GAS UNI POT...

Страница 20: ...F 1 GAS VALVE NATURAL Front Drain TS 037237 LP Front Drain TS 037238 NATURAL Rear Drain TS 037241 1 LP Rear Drain TS 037242 1 NATURAL All BB Models 037227 1 LP All BB Models 037228 ITEM QTY DESCRIPTIO...

Страница 21: ...1 800 KEATING GAS FRYER SERIES 2000 19 WIRING DIAGRAMS AA 2000 ELECTRICAL ASSEMBLY BB 2000 ELECTRICAL ASSEMBLY...

Страница 22: ...keatingofchicago com 20 TS 2000 ELECTRICAL ASSEMBLY not shown to scale BB ELECTRICAL ASSEMBLY WITH SAFE AND EASY FILTER not shown to scale...

Страница 23: ...1 800 KEATING GAS FRYER SERIES 2000 21 TS ELECTRICAL ASSEMBLY WITH SAFE EASY FILTER BASKET LIFT ELECTRICAL ASSEMBLY ALL FRYERS...

Страница 24: ...nty against latent defects Exclusions The warranties provided by Keating of Chicago Inc do not apply in the following instances 1 Defects arising out of or resulting from improper installation or main...

Страница 25: ...RANTY CARD ON OUR WEBSITE FOR YOUR CONVENIENCE COMPANY ADDRESS CITY STATE ZIP CODE DEALER NAME DATE OF PURCHASE INVOICE SERIAL MODEL I HAVE READ THE INSTALLATION AND OPERATING INSTRUCTIONS SIGNED DATE...

Отзывы: