background image

26

17) Decommissioning 

Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. 

It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant 

sample shall be taken. 

In case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is 

commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically
c) Before attempting the procedure ensure that:
Mechanical handling equipment is available, if required, for handling refrigerant cylinders.
All personal protetive equipment is available and being used correctly.
The recovery process is supervised at all times by a competent person.
Recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with manufacturer s instructions.
h) Do not overfill cylinders. (No more than 80% volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are 

removed from site promptly and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
18) Labelling 

Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and 

signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.
19) Recovery 

When removing refrigerant from a system, either for service or decommissioning, it is recommended good practice that all 

refrigerants are removed safely.
When tranferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that 

the correct numbers of cylinders for holding the total system charge are available. All cylinders to be used are designated for the 

recovered refrigerant and labelled for that refrigerant(i.e special cylinders for the recovery of refrigerant). Cylinders shall be complete 

with pressure relief valve and associated shut-off valves in good working order.
Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall 

be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good 

working order.
Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that 

it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent 

ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste 

Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain 

that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to retruning the 

compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is 

drained from a system, it shall be carried out safely.
20) Transportation, marking and storage for units 

Transport of equipment containing flammable refrigerants Compliance with the transport regulations.
Marking of equipment using signs Compliance with local regulations.
Disposal of equipment using flammable refrigerants Compliance with national regulations.
Storage of equipment/appliances.
The storage of equipment should be in accordance with the manufacturer’s instructions.
Storage of packed (unsold) equipment .
Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause 

a leak of the refrigerant charge.
The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations.

Содержание KSWP-70 DR8

Страница 1: ...h for purchasing our product Before using your unit please read this manual carefully and keep it for future reference Swimming pool heat pump INSTALLATION OWNER S MANUAL KSWP 70 DR8 KSWP 90 DR8 KSWP...

Страница 2: ...ssibly resulting in fire electrical shock property damage or personal injury Please drain water when the unit is not in use in winter to avoid freeze damage CONTENTS 1 SAFETY PRECAUTIONS 02 2 GENERAL...

Страница 3: ...START UP AND CONFIGURATION 8 1 Initial Start up At Low Outdoor Ambient Temperature 17 8 2 Pre operation Checks 17 8 3 Failure Diagnosis At First Installation 17 9 FINAL CHECKS AND TEST RUN 18 10 MAIN...

Страница 4: ...01 NOTE The pictures in this manual are for reference only please refer to the actual product...

Страница 5: ...8 only WARNING Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the...

Страница 6: ...ure to install a ground fault circuit interrupter may cause electric shocks and fire Make sure all wiring is secure Use the specified wires and ensure that terminal connections or wires are protected...

Страница 7: ...e collection facilities Contact your local goverment for information regarding the collection systems available If electrical appliances are disposed of in landfills or dumps hazardous substance can l...

Страница 8: ...wise it may lead to electromagnetic interference Power cords and communication wires should not come in contact with the refrigerant pipe so as to prevent the high temperature pipe from damaging wires...

Страница 9: ...hin the allowable ranges x Places where water leaking from the unit cannot cause damage to the location e g in case of a blocked drain pipe x Places where rain can be avoided as much as possible x Do...

Страница 10: ...te where the suction side may be exposed directly to wind To prevent exposure to wind install a baffle plate on the air discharge side of the unit In heavy snowfall areas it is very important to selec...

Страница 11: ...Check the strength and levelness of the installation floor ensure that the vibration and noise of the unit are minimized Bolts nuts gaskets shock pads foundations are not provided please purchase or c...

Страница 12: ...M8 4 Nut M8 4 Gasket M8 4 Solid foundation W H L 100 100 500 2 20 25 1 2 3 4 30 5 3 Drain Hole Position 31mm Drain hole Drain hole Connect to drain hose Drain connection For collecting the condensed...

Страница 13: ...stallation owner s manual of Wired controller 1 phase FUSE LPS NOTE The ground fault circuit interrupter must be 1 high speed type of 30mA 0 1s Stated values are maximum values see electrical data for...

Страница 14: ...units maximum allowable voltage range variation between phases is 2 3 Select circuit breaker that having a contact separation in all poles not less than 3 mm providing full disconnection where MFA is...

Страница 15: ...the first time 1 Open valve and charge water 2 Make sure that the pump and the water inlet pipe have been filled with water 3 Close the valve and start the unit Attention It is necessary that the wate...

Страница 16: ...5 Low pressure switch 15 Gas refrigerant temperature sensor 6 4 way valve 16 Liquid refrigerant temperature sensor 7 Fin coil heat exchanger 17 Water outlet temperature sensor 8 Ambient temperature se...

Страница 17: ...sembly unit Code Assembly unit 1 Compressor connection port U 5 Port for communication with main control board CN10 2 Compressor connection port V 6 Input port L for rectifier bridge CN1 3 Compressor...

Страница 18: ...Port for low pressure switch CN17 25 Port for transformer input CN40 7 Port for high pressure sensor CN3 Reserved 26 Reserved CN38 8 Port for TL temperature sensor CN7 Reserved 27 Reserved CN37 9 Port...

Страница 19: ...EVU ON If the heat pump in heating mode The heat pump automatically activates the boost function 3 SG ON EVU OFF The unit will operate normally 4 SG OFF EVU OFF The maximum running hours of the compr...

Страница 20: ...n connected properly and that the ground terminals are tightened Internal wiring Visually check the switch box for loose connections or damaged electrical components Mounting Check that the unit is pr...

Страница 21: ...leave the unit unattended when service panel is removed Refrigerant supplement Each unit has been equipped with sufficient refrigerant when leaving the factory Do not charge or change the refrigerant...

Страница 22: ...top panel 10 2 2 Titanium heat exchanger replace The titanium heat exchanger s remove and installation can only by loosening the copper tube at the top use welding torch WARNING Do not repair or repla...

Страница 23: ...20 10 2 3 Inverter drive board replace Remove the connecting wires from the inverter drive board before taking it out if necessary 1 2 3 4 5 6...

Страница 24: ...nsor T2 malfunction 17 H3 Gas refrigerant temp sensor T2B malfunction 18 H4 Three times L0 protecs 19 H6 The DC fan malfunction 20 H7 Voltage protection 21 H8 HP pressure sensor malfunction 22 HA Outl...

Страница 25: ...ks are ok the fault still exists please contact the installer or retailer 4 bA Ambient temp Out of operation range 1 Check whether the ambient temperature is lower than the operating range of the unit...

Страница 26: ...ty kW 4 50 5 20 7 00 7 80 8 60 EER 4 00 3 35 4 00 3 00 2 60 Sound pressure level 1m dB A 41 43 49 50 54 Silence mode sound pressure level 1m dB A 39 39 40 41 43 Water flow m h 3 1 3 9 5 4 6 9 8 3 Wate...

Страница 27: ...ng any hot work A degree of ventilation shall continue during the period that the work is carried out The ventilation should safely disperse any released refrigerant and preferably expel it externally...

Страница 28: ...m remote from the leak Oxygen free nitrogen OFN shall then be purged through the system both before and during the brazing process 15 Removal and evacuation When breaking into the refrigerant circuit...

Страница 29: ...mbers of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for t...

Страница 30: ......

Страница 31: ...NOTE 16125300003159 V C 16125300003159 V D...

Страница 32: ......

Отзывы: