7. Service terminal
Service terminal of the input and output is equipped to all types. Please use as occasion demands.
【
Type that is used
】
TSK-18, 23, 33, 42, 52, 56
RC
Connector for connection of Remote controller
This is the connector for connection of remote cable in
the case that the remote controller of the option is
E. S+
:
External sensor input terminal
E. S-
Necessary tool : No.1 Plus driver or 3mm Minus driver
E. C+
:
External temp. control input terminal
E. C-
Please connect the terminal of the external sensor K350A.
(K+
→
E. S+, K-
→
E. S- Tightening torque : 0.5N
・
m)
This is used in the case that temp. is controlled by other
temp. controllers. Please input SSR drive reverse action
output (DC12 - 24V). At this time, please use the temp.
controller of this machine as outlet temp. upper limiter.
E. R
External operation input terminal
This is used in the case that the hot-air generator is
operated by the outside signal. Input is for the contact
output. (Terminal voltage is less than DC12V 3.6mA.)
E. H
External heater input terminal
《
Input terminal
Mini terminal (Application electric wire Shield wire AWG24 - 16
Peel length 7 - 9mm) Tightening torque : 0.4N
・
m
This is used in the case that the heater is turned ON/OFF
by the outside signal. Input is for the contact output.
(Terminal voltage is less than DC12V 3.6mA.)
COM
Input common terminal
This is common for the external operation input terminal
E.R and external heater input terminal E.H.
Terminal voltage of the external operation input terminal E.R and external
heater input terminal E.H is less than DC12V 3.6mA. Please prepare the relay
that has the contact capacity that can open and close this voltage.
Please change the external operation mode by pushing the EXT. RUN switch of
this machine in the case that the external operation input and external heater
input is used.
《
Output terminal
》
Contact capacity is more than DC5V 10mA, less than DC30V 1A, Output common
BLW
Blow output terminal
This terminal becomes ON when the blower is operating.
Mini terminal (Application electric wire Shield wire AWG24 - 16 Peel length 7 - 9mm) Tightening torque :
Necessary tool : No.1 Plus driver or 3mm Minus driver
terminal total is less than 3A. (Unvoltage point of contact signal output)
HOT
Hot-air output terminal
This terminal becomes ON when the hot-air is operating.
T. W.
Temp. warning output
This terminal becomes ON at the time of the temp. warning.
T. A
Temp. alarm output
This terminal becomes ON when the temp. alarm was output.
BW
Blower warning output
This terminal becomes ON at the time of the blower warning.
OVH
Overheat output terminal
This terminal becomes ON at the time of overheat.
COM
Output common terminal
Protection circuit is not installed to unvoltage contact output. So, please do not connect the induction load (solenoid valve and
conductor etc.).
Attention
Please wire after the power supply is blocked without fail in the case that the service terminal is
used. You receive an electric shock if you wired in the condition which electricity is flowing. And,
please attach a terminal cover without fail after wiring.