*1
:
:
:
:
:
:
:
:
*
【
Type that is used
】
TSK-52HT, 62, 72, 82, 92, 102, 122, 132
《
Input terminal
》
M3 20P The upper row of the terminal Tightening torque : 0.5N
・
m
A1
External operation ON/OFF terminal
This is used in the case that the hot-air generator is operated by the
outside signal. Input is for the contact output. (Terminal voltage is less
A2
External heater ON/OFF terminal
This is used in the case that the heater is turned ON/OFF by the outside
signal. Input is for the contact output. (Terminal voltage is less than
A3
Input common terminal
This is common for the external operation ON/OFF terminal A1 and
external heater ON/OFF terminal A2.
A4, A5
External temp. control input terminal *1
This is used in the case that temp. is controlled by other temp.
controllers. Please input SSR drive reverse action output (DC11 - 24V).
At this time, please use the temp. controller of this machine as outlet
temp. upper limiter. (A4
→
+, A5
→
-)
A6, A7
External sensor input terminal
Please connect the terminal of the external sensor. (K+
→
A6, K-
→
A7
Terminal voltage of the external operation ON/OFF terminal A1 and
external heater ON/OFF terminal A2 is less than DC24V 7mA. Please
prepare the relay that has the contact capacity that can open and close
this voltage.
Please change the external operation mode by pushing the EXT. RUN
switch of this machine in the case that the external operation ON/OFF
and external heater ON/OFF is used.
A8,A9,A10
Terminal for connection of Remote controller
This is the terminal for connection of remote cable in the case that the
remote controller of the option is used. (For communication of the remote
Please input DC4 - 20mA only TSK-122 and 132. (4mA : Heater output
0%, 20mA : Heater output 100%)
《
Output terminal
》
M3 20P The Lower berth of the terminal Tightening torque : 0.5N
・
m
B1
Blow output terminal
Contact capacity is more than DC5V 10mA, less than DC30V 1A, Output common
terminal total is less than 3A. (Unvoltage point of contact signal output)
This terminal becomes ON when the blower is operating.
B2
Hot-air output terminal
This terminal becomes ON when the hot-air is operating.
B3
Temp. warning output terminal
This terminal becomes ON at the time of the temp. warning.
B4
Temp. alarm output terminal
This terminal becomes ON when the temp. alarm was output.
B5
Blower warning output terminal
This terminal becomes ON at the time of the blower warning.
B6
Overheat output terminal
This terminal becomes ON at the time of overheat.
B7
Output common terminal
B8,B9,B10
Terminal for connection of Remote controller
This is the terminal for connection of remote cable in the case that the remote controller of the option is used.
(For power supply of the remote controller)
Voltage DC24V has occurred to the remote controller power supply terminal B9-B10. Please never
short-circuit. Hot-air generator malfunctions without fail if short-circuits.
Attention
Please wire after the power supply is blocked without fail in the case that the service terminal is
used. You receive an electric shock if you wired in the condition which electricity is flowing. And,
please attach a terminal cover without fail after wiring.
Attention
Please do not unite or wire that was adjoined the wiring of the service terminal with the power
-7-