Precondition Password level 2 is activated.
QUADRO control mode is selected.
The display shows the operating mode.
1. Press «Enter».
The main menu is displayed.
2. Select the
< Configuration ➙ Control mode ➙ QUADRO > menu.
3. Press «DOWN» repeatedly until
Target is displayed as the active line.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.3.3 QUADRO
Menu
Min. run period
Target 240 s ¦ Actual 0 s
Active line setpoint value for minimum run-time
·········
Unloaded period
Target 240 s ¦ Actual 100 s
4. Press «Enter» to switch into setting mode.
The setpoint value
240 s flashes.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.3.3 QUADRO
Menu
Min. run period
Target 260 s ¦ Actual 0 s
Active line with changed setpoint value for minimum
run-time
·········
Unloaded period
Target 260 s ¦ Actual 100 s
Changed setpoint value for unloaded period
5. Use «UP» to change the minimum run-time.
6. Press «Enter» to accept the setting.
7. Change the unloaded period accordingly.
8. Press «Esc» repeatedly to return to the Main Menu.
Further information See chapter 4.7 for an overview of the control modes.
7.7 Activating the settings for the refrigerated dryer
Overview:
■ Set the operating mode
■ Output messages
7
Initial Start-up
7.7
Activating the settings for the refrigerated dryer
9_9450 03USE
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
77
Содержание ESD 352 SFC
Страница 5: ......
Страница 6: ......
Страница 7: ......
Страница 8: ......
Страница 9: ......
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 13: ......
Страница 14: ......
Страница 15: ......
Страница 16: ......
Страница 17: ......
Страница 18: ......
Страница 19: ......
Страница 20: ......
Страница 21: ......
Страница 22: ......
Страница 23: ......
Страница 24: ......
Страница 25: ......
Страница 26: ......
Страница 27: ......
Страница 28: ......
Страница 29: ......
Страница 30: ......
Страница 31: ......
Страница 32: ......
Страница 33: ......
Страница 34: ......
Страница 35: ......
Страница 38: ...Original instructions KKW SESD 2 02 en 05 ESD_2C_10357405_10 000_00 KKW SSC 2 02 05 20130903 095638...
Страница 42: ...Contents iv Service Manual Screw Compressor ESD 442 14 bar abs SFC SIGMA CONTROL 2 ESD_2C_10357405_10 LIN_00 E...
Страница 171: ...KKW SSC 2 03 en 01 BA SIGMA CONTROL FLUID KKW SSC 2 03 01 20130805 113302...
Страница 173: ......
Страница 175: ...Contents ii Quick user guide Controller SIGMA CONTROL 2 SCREW FLUID 1 1 3 9_9450 03 USE...
Страница 215: ...Contents iv Service manual Controller SIGMA CONTROL 2 SCREW FLUID 1 1 3 9_9450 03USE...
Страница 217: ...List of Illustrations vi Service manual Controller SIGMA CONTROL 2 SCREW FLUID 1 1 3 9_9450 03USE...
Страница 392: ...KKW GBASE 1 00 en ERSATZTEILE 10357405_10 ESD 2C 20130903 115349...
Страница 394: ...Contents ii Spare parts Screw compressor ESD 442 SFC 14 bar ESD 2C 1204 1205 No TTL ESD_2C_10357405_10_00 E...
Страница 396: ...List of Illustrations iv Spare parts Screw compressor ESD 442 SFC 14 bar ESD 2C 1204 1205 No TTL ESD_2C_10357405_10_00 E...
Страница 398: ...List of Tables vi Spare parts Screw compressor ESD 442 SFC 14 bar ESD 2C 1204 1205 No TTL ESD_2C_10357405_10_00 E...