PELLET BURNING STOVES INSTALLATION & MAINTENANCE MANUAL
37
Heat exchange tubes are
dirty.
Clean the heat exchange tubes.
10. Showing "Pressure
Erro" on the display
Vent pipe is blocked
The door is opening
The are some leakages
Shut down the stove, check the venting pipe
Close the door and unplugged then restart
Check it and repair it.
Adjust the combustion fan's speed up to offer more pressure in
the stove
NO increase in
temperature with stove in
operation
1. Incorrect combustion
adjustment.
2. boiler/system dirty
3. Insufficient stove
power.
4.poor pellet quality
1.check recipe and parameters.
2. check and clean the boiler
3.Check that stove is properly sized for the requirements of the
system.
4. Use
EN-A1-plus certified
pellets.
Condensation in boiler
1. Incorrect temperature
setting.
2.Insufficient fuel
consumption.
1. set the stove to a higher temperature.
2.check the recipe and/or technical parameters
Radiators cold in winter
1. room thermostat (local
or remote) set too low if
remote thermostat, check
if it is defective.
2. circulator does not run
because blocked.
3. Circulator does not run.
4.radiator have air in them
1.set to higher temperature or replace.( if remote)
2. free up the circulator by removing the plug and turning the
shaft with screwdriver.
3. check the electrical connections of the circulator; replace if
necessary
4.Vent the radiators
Hot water is not provided
1. circulator (pump)
blocked
1. free the circulator (pump)