——Parameter “Value send after the changed [1..2000]mA”
This parameter is visible when select “Send on change”. Set the change value that sending current
detection value should be reached. Options:
1..2000
For example, set 50mA. When the current value is 100mA, it need that the current current value is
more than 150mA or less than 50mA can send the current current value to the bus.
——Parameter “ Period of cyclical send [10..50000]s”
This parameter is visible when select “Send cyclically”. Set the time period that cyclically sending
current detection value. Options:
10..50000
Parameter “ Current threshold for ON [100..2000]mA”
This parameter is for setting the current threshold for power on. The device status is On when the
current is greater than or equal to the value. Options:
100..2000
Parameter “ Hysteresis value [0..50]mA”
This parameter is for setting the hysteresis value. The device status is Off when current value less
than (threshold - hysteresis value), no action in the interval. No hysteresis when the value is 0. Options:
0..50
Parameter “Send switch status”
This parameter is for setting whether to send switch status, and setting the sending conditions.
Switch status is sent to the bus by the object “Switch ON/OFF” Options:
No send
Send on change
Send cyclically
Send on read only
——Parameter “ Period of cyclical send [10..50000]s”
This parameter is visible when select “Send cyclically”. Set the time period that cyclically sending
switch status. Options:
10..50000