KNX/EIB
KNX Gateway for IR
19
Parameter “AC status response object”
This parameter is for setting whether to enable the AC status response object. When enabled, the
status objects of switch, fan speed, mode, setpoint temperature and swing are visible. And they will
send initial status to the bus when bus power on. Options:
Disable
Enable
Parameter “Window sensor”
This parameter is for setting whether to enable connect with the sensor that detect the switch
status of window. This is external sensor. Options:
Disable
Enable
——Parameter “Delay to turn off AC after window open [0..255]min”
This parameter is visible when the previous parameter enabled. Set the delay time for turning off
Air-condition when receive a command of opening window from sensor, to save energy. Options:
0..255
Parameter “Presence detector”
This parameter is for setting whether to enable connect with the presence detector. This is external
sensor. Options:
Disable
Enable
——Parameter “Delay to turn off AC after the room unoccupied [0..255]min”
This parameter is visible when the previous parameter enabled. Set the delay time for turning off
Air-condition when receive command of the room unoccupied from sensor, to save energy. Options:
0..255
Parameter “Object datatype of 1byte fan speed”
This parameter is for setting the object datatype of 1 byte fan speed. Options:
Fan stage (DPT_5.100)
Percentage (DPT_5.001)