CHAPTER 16
Grounding the SRX550 Services Gateway
IN THIS CHAPTER
SRX550 Services Gateway Grounding Specifications | 76
Grounding the SRX550 Services Gateway | 77
SRX550 Services Gateway Grounding Specifications
To meet safety and electromagnetic interference (EMI) requirements and to ensure proper operation, the
SRX550 Services Gateway must be adequately grounded before power is connected. You must provide
a grounding lug to connect the services gateway to earth ground.
WARNING:
Before services gateway installation begins, a licensed electrician must
attach a cable lug to the grounding and power cables that you supply. A cable with an
incorrectly attached lug can damage the services gateway (for example, by causing a
short circuit).
To ground the services gateway before connecting power, you connect the grounding cable to earth ground
and then attach the lug on the cable to the chassis grounding point, using the screw.
lists the specifications of the grounding cable used with the device.
Table 24: Grounding Cable Specifications for the SRX550 Services Gateway
Specification
Grounding Requirement
14 AWG single-strand wire cable
Grounding cable
Up to 25A
Amperage of grounding cable
Ring-type, Panduit LCC6-10A-L lug, or equivalent
Grounding lug
76
Содержание SRX550
Страница 1: ...SRX550 Services Gateway Hardware Guide Published 2020 12 16...
Страница 55: ...39...
Страница 137: ...4 PART Maintaining and Troubleshooting Components Maintaining Components 122 Troubleshooting Components 125...
Страница 178: ...162...
Страница 182: ...Restricted Access Warning 166...
Страница 196: ...Jewelry Removal Warning 180...
Страница 199: ...Operating Temperature Warning 183...
Страница 206: ...190...
Страница 210: ...194...
Страница 213: ...197...