CHAPTER 9
Cabinet Requirements
IN THIS CHAPTER
SRX550 Services Gateway Cabinet Size and Clearance Requirements | 47
SRX550 Services Gateway Cabinet Airflow Requirements | 48
SRX550 Services Gateway Cabinet Size and Clearance Requirements
You can install the SRX550 Services Gateway in a 19 in. (48.3 cm) cabinet as defined in Cabinets, Racks,
Panels, and Associated Equipment (document number EIA-310-D) published by the Electronic Industries
Alliance (
http://www.ecaus.org/eia/site/index.html
). You must mount the services gateway horizontally
in the cabinet.
NOTE:
The holes in the mounting brackets chassis are spaced 1.25 in (3.2 cm) apart, measured
from the center of the hole.
When selecting a cabinet, ensure that the physical characteristics of the cabinet comply with the following
specifications:
•
The cabinet is at least 2U (3.50 in. or 8.89 cm) and can accommodate the services gateway.
•
The outer edges of the mounting brackets extend the width of either chassis to 19 in. (48.2 cm), and the
front of the chassis extends approximately 0.5 in (1.27 cm) beyond the mounting brackets.
•
The minimum total clearance inside the cabinet is 30.7 in. (78 cm) between the inside of the front door
and the inside of the rear door.
NOTE:
A cabinet larger than the minimum required provides better airflow and reduces the
chance of overheating.
47
Содержание SRX550
Страница 1: ...SRX550 Services Gateway Hardware Guide Published 2020 12 16...
Страница 55: ...39...
Страница 137: ...4 PART Maintaining and Troubleshooting Components Maintaining Components 122 Troubleshooting Components 125...
Страница 178: ...162...
Страница 182: ...Restricted Access Warning 166...
Страница 196: ...Jewelry Removal Warning 180...
Страница 199: ...Operating Temperature Warning 183...
Страница 206: ...190...
Страница 210: ...194...
Страница 213: ...197...