Table 30: Cabinet Requirements and Specifications
(Continued)
Cabinet Requirement
Guidelines
Cabinet airflow requirements
When you mount the device in a cabinet, ensure that ventilation through
the cabinet is sufficient to prevent overheating, as follows:
•
Ensure adequate cool air supply to dissipate the thermal output of the
device or devices.
•
Ensure that the hot air exhaust of the chassis exits the cabinet without
recirculating into the device. An open cabinet (without a top or doors)
that employs hot air exhaust extraction from the top ensures the best
airflow through the chassis. If the cabinet contains a top or doors,
perforations in these elements assist with removing the hot air exhaust.
•
Install the device in the cabinet in a way that maximizes the open space
on the side of the chassis that has the hot air exhaust.
•
Route and secure all cables to minimize the blockage of airflow to and
from the chassis.
•
Ensure that the spacing of rails and adjacent cabinets is such that proper
clearance exists around the device and cabinet.
•
A cabinet larger than the minimum required provides better airflow and
reduces the chance of overheating.
Clearance Requirements for Airflow and Hardware Maintenance for
EX4100 and EX4100-F Switches
When planning the site for installing an EX4100 and EX4100-F switch, you must allow sufficient
clearance around the installed switch.
See:
•
for clearance requirements for airflow and hardware maintenance for
EX4100-24T, EX4100-24P, EX4100-48T, and EX4100-48P switches.
•
for clearance requirements for airflow and hardware maintenance for
EX4100-24MP and EX4100-48MP switches.
93
Содержание EX4100
Страница 1: ...EX4100 and EX4100 F Switch Hardware Guide Published 2022 11 08 ...
Страница 68: ...Figure 45 Front to Back Airflow Through the EX4100 48P or EX4100 48T Switch Chassis 59 ...
Страница 69: ...Figure 46 Front to Back Airflow Through the EX4100 24MP or EX4100 48MP Switch Chassis 60 ...
Страница 70: ...Figure 47 Front to Back Airflow Through the EX4100 F 24P Switch Chassis 61 ...
Страница 71: ...Figure 48 Front to Back Airflow Through the EX4100 F 24T Switch Chassis 62 ...
Страница 72: ...Figure 49 Front to Back Airflow Through the EX4100 F 48P Switch Chassis 63 ...
Страница 105: ...Figure 62 Clearance Requirements for Airflow and Hardware Maintenance for the EX4100 24MP and EX4100 48MP Switch 96 ...
Страница 106: ...Figure 63 Clearance Requirements for Airflow and Hardware Maintenance for the EX4100 F 24T Switch 97 ...
Страница 107: ...Figure 64 Clearance Requirements for Airflow and Hardware Maintenance for the EX4100 F 24P Switch 98 ...
Страница 108: ...Figure 65 Clearance Requirements for Airflow and Hardware Maintenance for the EX4100 F 48P Switch 99 ...
Страница 209: ...5 CHAPTER Troubleshoot Hardware Troubleshoot the EX4100 and EX4100 F Components 201 ...