c. Ensure that the pins are fully inserted into the terminal connector.
d. Use the screwdriver to tighten each screw on the terminal connector until snug. Do not
overtighten. Apply 4.5 lb-in. (0.51 Nm) of torque to the screws.
5. Insert the terminal connector (with the power cable attached) into the power supply socket on the
switch and secure it by tightening the two screws on either side of the terminal connector (see
Figure 91: Securing the Terminal Connector to the DC Power Inlet
NOTE: To supply sufficient power, terminate the DC input wiring on a facility DC source that
is capable of supplying a minimum of 7.5 A at –48 VDC.
6. Connect the other end of the power cable to the power source.
7. Close the input circuit breaker.
8. Verify that the IN OK and the OUT OK LEDs are lit green and on steadily.
Connect the EX4100 and EX4100-F Switch to
External Devices
IN THIS SECTION
Connect a Device to a Network for Out-of-Band Management | 145
144
Содержание EX4100
Страница 1: ...EX4100 and EX4100 F Switch Hardware Guide Published 2022 11 08 ...
Страница 68: ...Figure 45 Front to Back Airflow Through the EX4100 48P or EX4100 48T Switch Chassis 59 ...
Страница 69: ...Figure 46 Front to Back Airflow Through the EX4100 24MP or EX4100 48MP Switch Chassis 60 ...
Страница 70: ...Figure 47 Front to Back Airflow Through the EX4100 F 24P Switch Chassis 61 ...
Страница 71: ...Figure 48 Front to Back Airflow Through the EX4100 F 24T Switch Chassis 62 ...
Страница 72: ...Figure 49 Front to Back Airflow Through the EX4100 F 48P Switch Chassis 63 ...
Страница 105: ...Figure 62 Clearance Requirements for Airflow and Hardware Maintenance for the EX4100 24MP and EX4100 48MP Switch 96 ...
Страница 106: ...Figure 63 Clearance Requirements for Airflow and Hardware Maintenance for the EX4100 F 24T Switch 97 ...
Страница 107: ...Figure 64 Clearance Requirements for Airflow and Hardware Maintenance for the EX4100 F 24P Switch 98 ...
Страница 108: ...Figure 65 Clearance Requirements for Airflow and Hardware Maintenance for the EX4100 F 48P Switch 99 ...
Страница 209: ...5 CHAPTER Troubleshoot Hardware Troubleshoot the EX4100 and EX4100 F Components 201 ...