10
139262 Rev_H
9 / 11 / 2012
The cross-sectional area of the flue of a chimney with one
or more walls exposed to the outside below the roofline
may be no more than two times the cross-sectional area of
the stove flue collar.
If the chimney liner is too large to accommodate the stove,
an approved relining system must be installed to resize the
flue.
A new sheet metal damper block-off plate must be
installed around the connector pipe at the damper frame
and sealed with the proper sealant (usually High-Temp
Silicone).
3.3 Prefabricated Chimneys
When connecting the Jøtul F
50
TL
to a prefabricated
metal chimney always follow the pipe manufacturer’s
instructions and be sure to use the all components that are
required. This usually includes a “smoke pipe adapter” that
is secured to the bottom section of the metal chimney and
allows the chimney pipe to be secured to it with two sheet
metal screws. See fig. 11.
3.4 Mobile Home Installation
The Jøtul F 50 TL is approved for installation in
manufactured mobile homes provided the following
requirements are met:
1. All chimney components, including chimney sections,
supports, spark arrestor, etc., shall comply with the Standard
for Factory-built Chimneys for Residential Type and Building
Heating Appliances, UL 103 and/or CAN/ULC-S629 Standard
for 650°C Factory-built Chimneys.
2. The chimney shall be attached directly to the stove and
extend at least 3 ft. (0.9m) above the roof. Termination must
be at least 2 ft. (0.6m) above the hightest elevation of any
part of the mobile home within 10 ft. (3m).
3. In order to allow for transportation of the mobile home,
the chimney termination shall be readily removed at or
below an elevation of 13.5 ft. (4.1 m) above ground level and
reinstalled without use of special tools or instructions.
4. A spark arrester must be installed at the termination. The
net free area of the arrester above the chimney outlet must
not be less than four times the net area of the chimney
outlet, and the vertical height of the arrester must not
be less than one-half the diameter of the chimney flue.
Openings shall not permit the passage of a sphere having
a diameter larger than 1/2” (12.7 mm), and shall permit the
passage of a sphere having a diameter of 3/8” (9.6 mm).
5. Direct connection of the stove to an outside air source is
required. Use Outside Air Kit 157320. Do not substitute any
other connection method or device. See Appendix, Section
7.0. Duct termination must not be installed at a level that is
higher than the air inlet located at the bottom of the stove.
6. The stove must be secured to the mobile home floor. Use
Floor Bracket Kit 157321.
7. When the chimney exits the mobile home at a location
other than through the roof, and exits at a point 7 ft. (2.1 m)
or less above the ground level, a guard or other method of
enclosing the chimney, must be provided at the point of
exit for a height up to 7 ft. Openings of this chimney guard
shall not permit penetration of a 3/4 in. (19.1 mm) diameter
rod, or contact with the chimney by a 1/2 inch (12.7 mm)
diameter rod inserted through the opening a distance of
4 inches (102 mm).
8. Provision must be made for electrical grounding of the
chimney, chimney connector, and stove in accordance with
local building codes.
WARNING: Do not install this appliance in a sleeping room.
CAUTION: The structural integrity of the mobile home floor,
walls, and ceiling/roof must be maintained.
Listed Chimney
Specified
clearance
Attic
Insulation
Shield
Chimney
Connector
Figure 11. Prefabricated Listed Type HT Chimney.
Combustible
Ceiling Joists
Storm Collar
Listed Cap
Combustible
Ceiling Joists
Flashing
Chimney
Connector
Ceiling
Support
Chimney
Adaptor