 4.6

  Jøtul F 

50

 TL Clearance Specifications

UNPROTECTED WALLS

PROTECTED WALLS

 PER NFPA211 OR CAN/CSA -B365-M93

SIDE 

REAR

CORNER

SIDE

REAR

CORNER

Single Wall Connector

14”  / 356 mm

18” / 457 mm

12”  / 305 mm

12” / 305 mm

8” / 203 mm

8.5” / 216 mm

Single Wall Connector  

w/ Flue Collar Heat Shield

16” / 406 mm

10” / 254 mm

11” / 280 mm

8” / 203 mm

5” / 127 mm

6” / 153 mm 

 

   Double Wall Connector  

 

 

14” / 356 mm

9” / 229 mm

12”  / 305 mm

6”  / 152 mm

8” / 203 mm

6” / 152 mm

  Double Wall Connector   

  w/ Flue Collar Heat Shield

14” / 356 mm

6” / 152 mm

12”  / 305 mm

5” / 127 mm

6” / 152 mm

3.5” / 89 mm

Alcove w/ Double-Wall 

Connector

16”  / 406 mm

19” / 483 mm

N/A

6” / 152 mm

8” / 203 mm

N/A

 

 

   ­

 

 

€









€







 

 

­

€



Figure 16.  Clearance Diagrams. All specifications applicable to both top and rear exit configurations.

Содержание F50 TL Rangeley

Страница 1: ...Jøtul F 50 TL Rangeley Jøtul F 50 TL Rangeley Wood Stove Keep these instructions for future reference Installation and Operating Instructions for USA and Canada ...

Страница 2: ...k Screen 157232 Enjoy the warmth of open door fire viewing with use of this custom fit spark screen Stove Top Thermometer 5002 We recommend the use of a magnetic stove top ther mometer to monitor the surface temperature of the stove The optimum surface temperature range for the most efficient performance is between 4000 F 7000 F 2050 C 3160 C Outside Air Kit 157320 This kit includes a plenum assem...

Страница 3: ...use your new Jøtul F 50 TL wood stove Save these instructions and make them available to anyone using or servicing the stove Check Building Codes When installing operating and maintaining your Jøtul F 50 TL woodstove follow the guidelines presented in these instructions and make them available to anyone using or servicing the stove Your city town county or province may require a building permit to...

Страница 4: ... accidental contact by small children Install smoke detectors in the living areas and bedrooms of your home Test them regularly and install new batteries twice annually When installed in the same room as the stove a smoke detector should be located as far from the stove as possible to prevent it from sounding when adding fuel to the fire Avoid creating a low pressure condition in the room where th...

Страница 5: ... in the U S or in Canada CAN CSA B365 M and local codes 1 1 Unpack the Stove Inspect the stove for damage Contact your dealer immediately if any damage is found Do not install the stove if any damage is evident Contact your dealer Contents Top Load Door Tool BaffleHandleAssembly Bottom Heat Shield Flue Collar Heat Shield Stove Gloves 8 x 12 sheet metal screws 4 for Flue Collar Heat Shield M6 hex n...

Страница 6: ... from the stove bottom Remove the four pre installed M6 flange head hex nuts and use them to attach the shield See fig 4 1 5 Chimney Connector Use 6 single wall or listed 6 double wall stovepipe to connect the stove to the chimney Single wall stovepipe must be black steel or stainless steel and have a minimum thickness of 24 gauge Do not use aluminum or galvanized steel pipe for chimney connection...

Страница 7: ...in the temperatures necessary to maintain draft strength In extremely cold climates it may be necessary to reline the chimney or extend the height to help establish draft A tall interior masonry chimney is easier to keep warm and will perform the best under a variety of weather and environmental conditions The following guidelines give the necessary chimney requirements based on the national code ...

Страница 8: ...nd at least 2 feet 61 cm higher than the highest part of the roof or structure that is within 10 feet 3 05 m of the chimney measured horizontally Chimneys shorter than 14 feet 4 27 m may not provide adequate draft Inadequate draft can result in smoke spillage when loading the stove or when the door is open Poor draft can also cause back puffing ignition of gas build up inside the firebox and slugg...

Страница 9: ...d requires the removal of all combustible materials from at least 18 45 7 cm around the chimney connector s proposed location A 6 round liner requires a minimum opening 43 x 43 109 2 x 109 2 square Locate the pass through at least 18 from combustible ceiling materials The space that is cleared of combustible materials must remain empty Sheet metal panels can be used to cover the area However when ...

Страница 10: ...alled without use of special tools or instructions 4 A spark arrester must be installed at the termination The net free area of the arrester above the chimney outlet must not be less than four times the net area of the chimney outlet and the vertical height of the arrester must not be less than one half the diameter of the chimney flue Openings shall not permit the passage of a sphere having a dia...

Страница 11: ...those that are visible and also include materials that are behind noncombustible materials If you are not sure of the combustible nature of a material consult your local fire officials Remember Fire Resistant materials are considered combustible they are difficult to ignite but will burn Also Fire rated sheet rock is also considered combustible Contact your local building officials about restricti...

Страница 12: ... 13 Alcove with Unprotected Walls Figure 14 Alcove with Wall Protection Figure 15 Hearthmount Clearances 4 4 Alcove Installation The Jøtul F 50 TL can be installed in an alcove as diagrammed in figs 13 14 1 The stove must be installed only with double wall chim ney connector 2 Wall and ceiling protection if used must extend over the entire area 3 Alcove floor protection must consist of a UL ULC or...

Страница 13: ...w Flue Collar Heat Shield G 16 406mm H 10 254 mm I 11 280 mm J 8 203 mm K 5 127 mm L 6 153 mm Double Wall Connector M 14 356 mm N 9 229 mm O 12 305 mm P 6 152 mm Q 8 203 mm R 6 152 mm Double Wall Connector w Flue Collar Heat Shield S 14 356 mm T 6 152 mm U 12 305 mm V 5 127 mm W 6 152 mm X 3 5 89 mm Alcove w Double Wall Connector A 16 406 mm B 19 483 mm N A D 6 152 mm E 8 203 mm N A Figure 16 Clea...

Страница 14: ...also determines the effectiveness of the air wash over the glass the higher the setting the cleaner the glass Additional air is separately directed into the top of the fire chamber to support combustion of exhaust gasses before passing out of the stove This unregulated Secondary Air enters through an inlet in the rear of the stove bottom and is heated as it passes through the rear of the stove int...

Страница 15: ...ak in procedure for your stove Use a magnetic stove top thermometer to monitor stove temperature placed directly on the cook plate Set the Primary Air Shutter fully open all the way to the right 1 Light a small fire of newspaper and kindling at the front of the stove Gradually add small pieces of wood but only allow the stove to reach a maximum surface temperature of 200 F 93 C Continue burning at...

Страница 16: ...are available to the stove when using the spark screen 5 7 Starting and Maintaining a Fire Burn only solid wood directly on the bottom grate of the stove Do not elevate the fire in any way WARNING DO NOT OPERATE THIS STOVE WITH THE ASH DOOR OPEN DOING SO MAY CAUSE DAMAGE AND WILL VOID YOUR WARRANTY We recommend use of a magnetic stovetop thermometer to monitor the surface temperature of the stove ...

Страница 17: ...the fire Opening the door will only supply additional oxygen and intensify the fire When the fire in the flue has subsided resist the temptation to open the door to check on the fire The fire may have suffocated but could re ignite with a supply of fresh air After a chimney fire do not use the stove until the chimney connector and flue have been cleaned and inspected to ensure no damage has been s...

Страница 18: ...ing the glass Never use the door to push wood into the firebox If the glass becomes cracked or broken follow the replacement procedure below Never operate the stove with a cracked or broken glass panel 6 0 Maintenance 6 1 Door Latch Adjustment Over time as the door gasket becomes compressed it may be necessary to adjust the door latch in order to maintain the integrity of the door seal To check th...

Страница 19: ...e gasket clamp as shown in fig 20 Close and latch the door and then reopen Wipe away any excess cement that may have squeezed out from around the gasket 6 5 Glass Removal or Replacement See fig 20 1 Place the door face down on a protected surface 2 First just loosen each glass clip screw and then remove the clips 3 Lift the glass panel out of the door Use pliers and a putty knife to remove the old...

Страница 20: ... Tools Required 10 mm wrench or socket driver pliers 1 4 socket driver or flat head screwdriver 4 mm hex key work gloves 2 Attach the Air Deflector See figs 21 and 22 3 Use pliers to bend the deflector tabs at the perforation lines as shown Attach the deflector to the interior side of the rear shroud using two 8 X 12 sheet metal screws from the exterior side 3 Attach the Blower Mounting Bracket Us...

Страница 21: ...ts power source before cleaning or servicing Regular cleaning will help ensure you obtain maximum life from the blower Use a vacuum with a soft brush attachment to clean the blower fans and motor housing at least monthly or more frequently if there are pets in the home Keep the area under the stove free of dust and debris 8 Route the power cord to the nearest electrical outlet 9 10 1 2 3 5 6 7 4 4...

Страница 22: ...ent Screen 4 Duct Clamps 2 The exterior air inlet should not be installed at a level higher than the stove bottom 1 Assembly will be easier with the Ash Door removed Release the cotter pin to remove the hinge pin 2 Attach the Duct Collar to the Main Manifold using four 8 x 12 mm sheet metal screws 3 Remove the four nuts from the studs protruding from the stove bottom Figure 26 Front Manifold place...

Страница 23: ...e corners and secure each to the floor using an appropriate length lag screw 4 Orient the Front Manifold Panel as shown in figs 25 and 26 Set it in place above the ash housing between the front legs of the stove 5 Attach the Main Manifold to the four studs on the stove bottom and the two studs on the Front Manifold using the hex head nuts provided 6 Attach the Outside Air Bottom Heat Shield to the...

Страница 24: ...24 139262 Rev_H 9 11 2012 Figure 29 F 50 TL Illustrated Parts ...

Страница 25: ...atch 224733 52 Offset Latch Front Door Nickel Plated 157459 53 Front Door Tool Nickel Plate 157262 53a Receiver 224359 53b Wooden Handle 128064 53c M6 Rod 126835 53d Nut Housing 224358 8 0 Jøtul50TLRangeleyPartList No Description Part 58 Washer Hinge M6 12mm OD x 6mm ID x 0 5mm Zinc 117588 60 Gasket LD 250 Fiberglass Rope 200024 61 Glass Ceramic Door 50 TL 224158 62 Glass Clip w Gasket Top Steel S...

Страница 26: ... to wood burning products identified by Jøtul trade names as set forth below A Limited Lifetime Warranty Parts Only Jøtul North America Inc JØTUL warrants to the original retail purchaser that those baffle and air manifold components of the Jøtul Stove or Fireplace Insert specified above will be free of defects in material and workmanship for the life of the stove This warranty is subject to the t...

Страница 27: ...27 139262 Rev_H 9 11 2012 This page is intentionally blank ...

Страница 28: ...038 USA Quality Jøtul AS utilizes quality controls conforming to NS EN ISO 9001 for product development manufacturing and distribution of stoves and fireplaces This policy is intended to provide you with the peace of mind that the Jøtul product you purchase meets or exceeds current uniform standards for quality and safety a continuation of the standards instituted at the company s inception in 185...

Отзывы: