EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(9) Protection of Decrease in Outlet Temperature for Cooling (Function Setting “Fb”)
Press “PSW3” and select the setting condition “0” to “3” at Protection of Decrease in Outlet Temperature for
Cooling “
”, can be set. When the indoor unit outlet air temperature falls at cooling operation, the
compressor frequency forcibly decreases to prevent a drop in outlet air temperature. If the outlet
temperature decreases and the temperature is less than the Thermo-OFF condition even after the
compressor frequency decreases, the indoor unit becomes Thermo-OFF condition.
(When Thermo-OFF is activated under this condition, the operation will be restarted after three minutes.)
"Fb" Setting Condition
Outlet Temperature
Target Value
at Thermo-OFF
0
-
-
1
50
o
F (10
o
C)
44
o
F (7
o
C)
2
54
o
F (12
o
C)
48
o
F (9
o
C)
3
58
o
F (14
o
C)
52
o
F (11
o
C)
(8) Wave Function Setting (Function Setting “UE”)
Press “PSW3” and select the setting condition “0” to “4”, so that Wave Function Setting “
” can be set.
While this function is activated, the maximum limit of running current is changed from 40% to 80% as shown
LQWKH¿JXUH
NOTE:
If Demand Current Control by External Input Function is set and the external input signal is available, this
function is not performed during Demand Current Control by External Input Function is performed.
"UE" Setting Condition
Running Current Lower Limit Setting
0
Not Available (Default Seting)
1
40%
2
60%
3
70%
4
80%
NOTE:
The current limit value is targeted value. The actual current value may temporarily be higher than the value
shown in the table above depending on the operating control condition.
When the scheduled operation of “Demand Function Setting” is set from the central controller, refer to
the “Installation and Maintenance Manual” for the central controller.
20min. 10min. 20min. 10min. 20min.10min. 20min.
Electricity
Consumption
(100%)
Electricity
Consumption
(40 to 80%)
*In this section, Thermo-ON/Thermo-OFF mean for the indoor unit.
Thermo-ON: The indoor unit is running.
Thermo-OFF: The indoor unit stays on, but doesn’t run.
Содержание YVAHP0721CW Series
Страница 2: ......
Страница 10: ...viii SM 16007 ...
Страница 14: ......
Страница 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Страница 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Страница 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Страница 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Страница 262: ... SM 16007 TROUBLESHOOTING Surge Absorber SA Surge Absorber SA Surge Absorber SA 3RVLWLRQ RI 6XUJH EVRUEHU 9 9 1 1 1 ...
Страница 284: ......
Страница 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Страница 360: ......
Страница 361: ...SM 16007 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting ...
Страница 390: ......
Страница 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Страница 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Страница 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Страница 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...