3-48
SM-16007
TROUBLESHOOTING
*1): When replacing or checking for the inverter part, make sure to perform the electric discharge work according to
Section 4.2.1.1 “High Voltage Discharge Work for Replacing Parts”.
*2): When replacing or checking for the fan controller, make sure to perform the electric discharge work according to
Section 4.2.1.1 “High Voltage Discharge Work for Replacing Parts”.
*3): When the fuse for the fan controller is blown, the fan controller may be broken too.
In this instance, the fan controller should be replaced.
Cause
Check Item
Action
(Turn OFF Main Switch)
Event
Check conduction.
Check for loose
screw connections.
Replace or repair
wires, or tighten screws.
Check connection Nos.
Correctly connect wires.
Check connection.
Repair wiring
connection.
Replace PCB if faulty.
Replace power fuse,
power transistor, and
diode module.
Replace incoming
current limit resistance.
Between O.U. PCB,
Inverter PCB and
Fan Controller
Disconnected
Wires,
Contact Failure or
Incorrect
Connection
Check continuity of
wires.
Check for loose
screw connections.
Check connection No.
Replace or repair
wires, tighten screws
or correct wires.
Power Source Wiring
for Outdoor Unit
Disconnected Wires
to PCB
Faulty PCB
Blown Power Fuse
Disconnected
Incoming Current Limit
Resistance
Check conduction of
power fuse, power
transistor, diode module.
Check resistance of
incoming current limit
resistance.
Disconnected Wires,
Contact Failure
Incorrect Wiring
Incorrect Wiring
Failure of
O.U. PCB,
Inverter PCB and
Fan Controller
Failure of
Electrical
Components
Power Fuse,
Resistance
Blown Fuse
(Fan Controller)
Check conduction
of fuse.
Replace Fan Controller
if faulty *3)
Содержание YVAHP0721CW Series
Страница 2: ......
Страница 10: ...viii SM 16007 ...
Страница 14: ......
Страница 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Страница 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Страница 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Страница 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Страница 262: ... SM 16007 TROUBLESHOOTING Surge Absorber SA Surge Absorber SA Surge Absorber SA 3RVLWLRQ RI 6XUJH EVRUEHU 9 9 1 1 1 ...
Страница 284: ......
Страница 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Страница 360: ......
Страница 361: ...SM 16007 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting ...
Страница 390: ......
Страница 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Страница 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Страница 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Страница 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...