Alarm
Code
Activation of Protection Device for Indoor Fan Motor
(Indoor Unit with DC Motor)
O
7KH581LQGLFDWRUUHGÀDVKHV
O
The indoor unit number (refrigerant cycle number - address number), the alarm code, the model code*
1)
,
the model name*
1)
and the number of connected indoor units are displayed on the LCD. The indoor unit
number and the alarm code are displayed on the 7-segment display of the outdoor unit PCB.
*1) Except for some models.
+
7KLVDODUPFRGHLVGLVSOD\HGZKHQWKHLQGRRUIDQPRWRUURWDWHVDWOHVVWKDQUSPIRU¿YHVHFRQGV
three times in 30 minutes during the operation.
Failure of I.U. PCB
Failure of I.U. PCB
Failure of I.U. PCB
Failure of I.U. PCB
(*1)
The electrical source for I.U. PCB
is not supplied when LED4
is turned OFF.
(*2)
Abnormal voltage is supplied
for fan motor.
Is LED4 on
I.U. PCB OFF?
(*1)
Is LED5 on
I.U. PCB OFF?
(*2)
Check connectors PCN7
and CN1 on I.U. PCB.
Yes
Replace I.U. PCB.
No
No
No
No
Failure of I.U. PCB
Replace I.U. PCB.
Is fan motor
speed control command to
fan motor sent correctly?
(*5)
Yes
Yes
Is DC power
output of I.U. PCB
normal? (*3)
Replace I.U. PCB.
Replace I.U. PCB.
Replace I.U. PCB.
(*3)
Measure the voltage between VCC15
and VDC - (15V+10%) with a tester.
Yes
Yes
No
Occurrence of
Alarm Code “19”
(*4)
Measure the voltage of the following check points with a tester.
Between VCC05 and GND: 5V+4%
Between VCC13 and GND: 13.1V+10%
(Normal Voltage: DC311 - 339V)
No
Failure of Fan Motor
Replace Fan Motor
Yes
Failure of I.U. PCB
Failure of Fan Motor
Is speed pulse
signal to I.U. PCB
sent correctly?
(*6)
Replace I.U. PCB.
Replace Fan Motor.
No
Does Fan
Motor run?
Yes
(*5)
(*6)
(*6) Start the operation with CN1 on I.U. PCB connected.
It functions normally if several volts are generated between
No.2 pin of PC4 and VDC- (check point).
(NOTE)
Even if the operation is stopped, approx. 0.2V can be generated.
Yes
Check that 208/230V is
applied between
L1 and N of TB1.
NOTE:
Turn OFF the power source
completely before connector
checking. Otherwise, it may cause
a DC fan motor failure.
(Built-in PCB for the DC fan
motor may be damaged.)
(*5) Start the operation with CN1 on I.U. PCB disconnected.
It functions normally if more than 1V is generated between
No.3 pin of CN1 and VDC- (check point) for approx. 10 seconds
after starting the operation.
(NOTES)
1. Even if the operation is stopped, 0.3 to 0.4V can be generated.
2. To perform the operation “
H
”, no voltage will be generated
sequentially 10 seconds after start of operation.
Is DC power
output of I.U. PCB
normal? (*4)
l
Perform the following
check after setting the
air flow volume to “HIGH”.
l
A high voltage is applied
to electrical parts. Perform
the check carefully to
prevent an electric shock.
(Normal Voltage: DC280V)
Ɣ3HUIRUPWKHIROORZLQJ
check after setting the
DLUÀRZYR,*+´
Ɣ$KLJKYROWDJHLVDSSOLHG
to electrical parts. Perform
the check carefully to
prevent an electric shock.
Check that 208/230V is
applied between
L1 and L2 of TB1.
Содержание YVAHP0721CW Series
Страница 2: ......
Страница 10: ...viii SM 16007 ...
Страница 14: ......
Страница 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Страница 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Страница 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Страница 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Страница 262: ... SM 16007 TROUBLESHOOTING Surge Absorber SA Surge Absorber SA Surge Absorber SA 3RVLWLRQ RI 6XUJH EVRUEHU 9 9 1 1 1 ...
Страница 284: ......
Страница 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Страница 360: ......
Страница 361: ...SM 16007 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting ...
Страница 390: ......
Страница 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Страница 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Страница 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Страница 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...