SM-16007
5-21
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(3) Cancellation of Outdoor Ambient Temperature Limit (Function Setting “GS”)
Press “PSW3” and select the setting condition “0” to “3” for Cancellation of Outdoor Ambient Temperature
limit “
”. Then, this function can be set.
The heating operation is continued even under a high outdoor temperature or the cooling operation is
continued even under a low temperature.
NOTE:
,IWKLVIXQFWLRQLVVHWDQGWKHRXWGRRUXQLWRSHUDWHVLQWKHRSHUDWLRQVWRSSDJHDUHDVKRZQLQWKHDERYH¿JXUH
for a long time, some alarm codes by abnormal operation may occur and the outdoor unit may be damaged
since outdoor ambient temperature limit control is cancelled.
If the alarm codes occur frequently, contact your distributor or contractor.
“GS” Setting Condition
Operation Mode for Cancellation
0
Not Available (Default Setting)
1
Heating
2
Cooling
3
Heating/Cooling
Heating Operation
Indoor
Inlet Air
Temperature
[
o
F (
o
C)]
Outdoor Temperature [
o
F (
o
C)]
Operation
Stoppage
Area
77 (25)
0
(-18)
62
(17)
59
(15)
66
(19)
78
(26)
80 (27)
86 (30)
The limitation of the permissible outdoor
temperature area in heating operation
(factory setting) shown in the figure at the right
is cancelled.
NOTE:
When the outdoor ambient temperature
limit for heating operation is cancelled,
the operation may stop due to increasing
high pressure since the protection control
is not cancelled.
Cooling Operation
The limitation of the permissible outdoor
temperature area in cooling operation
(factory setting) shown in the figure at the right
is canceled.
Indoor
Inlet Air
Temperature
[
o
F (
o
C)]
Outdoor Temperature [
o
F (
o
C)]
Operation
Stoppage
Area
8
(-13)
95
(35)
70 (21)
80 (27)
NOTE:
When the outdoor ambient temperature
limit for cooling operation is cancelled,
the operation may stop due to decreasing
low pressure since the protection control
is not cancelled.
Содержание YVAHP0721CW Series
Страница 2: ......
Страница 10: ...viii SM 16007 ...
Страница 14: ......
Страница 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Страница 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Страница 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Страница 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Страница 262: ... SM 16007 TROUBLESHOOTING Surge Absorber SA Surge Absorber SA Surge Absorber SA 3RVLWLRQ RI 6XUJH EVRUEHU 9 9 1 1 1 ...
Страница 284: ......
Страница 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Страница 360: ......
Страница 361: ...SM 16007 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting ...
Страница 390: ......
Страница 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Страница 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Страница 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Страница 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...