SM-16007
1-51
INSTALLATION
Be sure to note the following points when running cables under the unit using conduit tubing.
(The pipe cover needs to be removed before performing piping and wiring.)
Tightly secure the power supply wiring using a cable clamp inside the unit.
NOTES:
:KHQLQVWDOOLQJWKHSRZHUVXSSO\ZLULQJXVHWKH¿HOGVXSSOLHGFRQGXLWWXEHDVVKRZQEHORZ
Remove the rubber bushing from the unit for the conduit tubing installation.
2. When installing the communication cables, run them through the rubber grommet attached to the unit.
3. Maintain at least 5 inch (127mm) between the power supply wiring and communication cables.
4. Prevent cables from touching or rubbing up against refrigerant piping, plate edges, and electrical
components inside the unit.
5. Completely seal the end of conduit tube with sealing materials to prevent the rain from entering the
conduit tube. (In case of wiring from bottom base)
6. Create a drainage hole at the lowest part of the conduit tube. (In case of wiring from bottom base)
7.4 Electrical Wiring Connections of Indoor Unit, and Outdoor Unit
(1) Connect a power supply wiring to each outdoor unit. Connect a Ground Fault Circuit Interrupter (GFCI),
fuse, and main switch (S) to each outdoor unit.
(2) Connect a power supply wiring to each indoor unit group connected to the same outdoor unit. (Total
operating current be less than 12A.)
Connect a Ground Fault Circuit Interrupter (GFCI), fuse, and main switch (S) to each indoor unit group.
(3) Connect the communication cable between indoor units, and outdoor units, as shown in Figure 7.1.
(4) Connect the communication cables in the same refrigerant system unit. (If the refrigerant piping of
indoor unit is connected to the outdoor unit, also connect the communication cables to the same indoor
unit.) Connecting the refrigerant piping and communication cables to the different refrigerant systems
may lead to malfunction.
(5) Use communication cabling that is a minimum of AWG18 (0.82mm
2
), 2-Conductor, Stranded Copper.
Shielded cable must be considered for applications and routing in areas of high EMI and other sources
of potentially excessive electrical noise to reduce the potential for communication errors. When
shielded cabling is applied, proper bonding and termination of the cable shield is required as per
Johnson Controls guidelines. Plenum and riser ratings for communication cables must be considered
per application and local code requirements. (Do not use Tri-Core or anything beyond.)
Power Supply Wiring
Seal
Conduit Tube
Communication Cable
Rubber Bushing
For Wiring from Bottom Base
Rubber Bushing
Communication Cable
Conduit Tube
For Wiring from Front Piping Cover
Содержание YVAHP0721CW Series
Страница 2: ......
Страница 10: ...viii SM 16007 ...
Страница 14: ......
Страница 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Страница 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Страница 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Страница 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Страница 262: ... SM 16007 TROUBLESHOOTING Surge Absorber SA Surge Absorber SA Surge Absorber SA 3RVLWLRQ RI 6XUJH EVRUEHU 9 9 1 1 1 ...
Страница 284: ......
Страница 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Страница 360: ......
Страница 361: ...SM 16007 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting ...
Страница 390: ......
Страница 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Страница 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Страница 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Страница 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...