5-10
SM-16007
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
• Setting Example
Forced Stoppage at Input 2 (between 2 and 3 pins of CN17)
• Setting Example
Demand Current Control at Input 2 (between 2 and 3 pins of CN17), Control Function No. 6 to 10
(5)
Input
Demand Current Control 40, 60, 70, 80, 100% (Control Function No.6 to 10)
When the input terminals for Demand Current Control on the outdoor unit PCB are short-circuited, the
compressor frequency is controlled so that the maximum limit of the outdoor running current is set to 100%,
80%, 70%, 60% or 40% of the reference power consumption.
If the outdoor unit running current exceeds the maximum limit for twenty minutes, the indoor unit is put
under Thermo-OFF condition. In this case, the stoppage code No. “10” is given. When the input terminal is
opened during the demand current control, its control is released.
(4)
Input
Forced Stoppage (Control Function No.5)
When the input terminals for Forced Stoppage on the outdoor unit PCB are short-circuited while running,
the compressors and the indoor fan motors are stopped. The stoppage code No. “10” is given.
In this case, if the input terminals are opened, operation is resumed.
< NOTE >
1. The Demand Current Control (%) is value criterion. The value used for this control is calculated from
the current, and therefore is different from the value indicated by a wattmeter. If it is required that the
PD[LPXPSRZHUFRQVXPSWLRQLVPDQDJHGSUHFLVHO\D¿HOGVXSSOLHGGHPDQGFRQWUROOHUVKRXOGEHXVHG
2. The actual value may temporarily be higher than the indicated value (by 40% to100%) depending on the
operating control conditions such as protection control.
NOTE:
Thermo-ON: The outdoor unit and some indoor units are running.
Thermo-OFF: The outdoor unit and some indoor units stay on, but don’t run.
Outdoor Unit
Capacity
[MBH]
Reference Power
Consumption
[KW]
072, 096
9.6
NOTE:
When demand control (ON/OFF) is performed, it is recommended that the control (ON/OFF) time is set
appropriately according to the heat load. Also, set the demand control time approximately once in 15
minutes at the minimum in consideration for saving energy.
*Thermo-ON: The outdoor unit and some indoor units are running.
Thermo-OFF: The outdoor unit and some indoor units stay on, but don’t run.
X1: Auxiliary
Relay
SS3: Demand Current Switch
Control Circuit
X1
2
3
1
2
3
3P Connector
Outdoor Unit
PCB
CN17
SS3
Power
Source
X1
Wiring Diagram Example of Demand Current Control
Wiring Diagram Example of Forced Stoppage
X1: Auxiliary
Relay
SS3: Forced Stoppage Switch
Control Circuit
X1
2
3
1
2
3
3P Connector
Outdoor Unit
PCB
CN17
SS3
Power
Source
X1
Содержание YVAHP0721CW Series
Страница 2: ......
Страница 10: ...viii SM 16007 ...
Страница 14: ......
Страница 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Страница 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Страница 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Страница 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Страница 262: ... SM 16007 TROUBLESHOOTING Surge Absorber SA Surge Absorber SA Surge Absorber SA 3RVLWLRQ RI 6XUJH EVRUEHU 9 9 1 1 1 ...
Страница 284: ......
Страница 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Страница 360: ......
Страница 361: ...SM 16007 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting ...
Страница 390: ......
Страница 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Страница 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Страница 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Страница 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...