5-16
SM-16007
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
5.3.2.1 Function Setting Item
No.
Setting Item
7-Segment
Display
Contents
SEG2 SEG1
1
Circulator Function
at Heating Thermo-OFF
No setting
Indoor fan forced ON and OFF (2 min. ON / 6 min. OFF)
Indoor fan forced ON and OFF (2 min. ON / 13 min. OFF)
Indoor fan forced ON and OFF (2 min. ON / 28 min. OFF)
Indoor fan stop
2
Night Shift (Low Noise)
No Setting
Setting of night shift 1
Setting of night shift 2 (Cooling Only)
3
Cancellation of Outdoor Ambient
Temperature Limit
No setting
For heating
For cooling
For cooling/heating
4
Not Prepared
-
5
SLo (Fan Speed)
Defrost Setting
Indoor fan stop when heating operation is activated/during defrost operation
Indoor fan SLo operation during defrost operation
Indoor fan SLo operation when heating operation is activated
Indoor fan SLo operation when heating operation is activated/ during defrost
operation
Indoor fan SLo operation when heating operation is activated
(including Start Up after Defrost)
Indoor fan intermittent operation during hot gas bypass defrosting
6
Cancellation of Hot Start
Hot start control is available
Cancellation of hot start
7
Priority Capacity Mode
No setting
Change of frequency maximum limit value
Change of current limit value
Change of frequency maximum limit value and current limit value
8
Compressor Frequency Control
Target Value for Cooling
Initial setting (Ps evaporation temperature targeted value 46
o
F (8
o
C)
Targeted value 36
o
F (2
o
C)
Targeted value 38
o
F (3
o
C)
Targeted value 40
o
F (4
o
C)
Targeted value 41
o
F (5
o
C)
Targeted value 42
o
F (6
o
C)
Targeted value 44
o
F (7
o
C)
Targeted value 48
o
F (9
o
C)
Targeted value 50
o
F (10
o
C)
Targeted value 52
o
F (11
o
C)
Targeted value 54
o
F (12
o
C)
Targeted value 56
o
F (13
o
C)
Targeted value 58
o
F (14
o
C)
9
Compressor Frequency Control
Target Value for Heating
Initial setting (Pd targeted value 413psi (2.85MPa))
Targeted value 392psi (2.70MPa)
Targeted value 399psi (2.75MPa)
Targeted value 406psi (2.80MPa)
Targeted value 409psi (2.82MPa)
Targeted value 418psi (2.88MPa)
Targeted value 421psi (2.90MPa)
Targeted value 428psi (2.95MPa)
10
Indoor Expansion Valve Control
Target Value for Cooling
Initial setting (SH targeted value +9
o
F (+5
o
C))
SH Targeted value +13
o
F (+7
o
C)
SH Targeted value +11
o
F (+6
o
C)
SH Targeted value +7
o
F (+4
o
C)
SH Targeted value +5
o
F (+3
o
C)
11
Indoor Expansion Valve Control
Target Value for Heating
Initial setting (SC targeted value +9
o
F (+5
o
C))
SC Targeted value +20
o
F (+11
o
C)
SC Targeted value +15
o
F (+8
o
C)
SC Targeted value +3
o
F (+2
o
C)
SC Targeted value -2
o
F (-1
o
C)
Содержание YVAHP0721CW Series
Страница 2: ......
Страница 10: ...viii SM 16007 ...
Страница 14: ......
Страница 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Страница 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Страница 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Страница 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Страница 262: ... SM 16007 TROUBLESHOOTING Surge Absorber SA Surge Absorber SA Surge Absorber SA 3RVLWLRQ RI 6XUJH EVRUEHU 9 9 1 1 1 ...
Страница 284: ......
Страница 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Страница 360: ......
Страница 361: ...SM 16007 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting ...
Страница 390: ......
Страница 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Страница 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Страница 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Страница 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...