Table 24: Alarm list
Button label (alarm
name)
Cause of alarm and condition to reset
Countermeasures
Gene. Hi Conce. Prevent.
(Generator High
Concentration Prevention
Control)
Generator solution concentration rose, then load
limit operation was applied. The alarm resets if
concentration has been lower than the defined value
for determined period
•
Check the cooling water line.
•
Check the cooling water flow rate.
•
Check the cooling tower.
•
Purge manually (according
to instructions shown in
).
•
Contact your local Johnson Controls
Service Center.
Record. Sensor Abnormal
(Recording Sensor
Abnormal)
Chilled water inlet temperature sensor, cooling
water inlet temperature sensor, and/or absorber
temperature sensor detected abnormal value due
to disconnection, short circuit, power outage, and so
on. Remote setting signal is abnormal during remote
SP mode (remote chilled water outlet temperature
setting mode). The hot water control valve opening
limit signal is abnormal while the upper limit input is
enabled. Alarm resets after the temperature or signal
returns to normal.
•
Check the remote setting signal.
•
Tighten the terminal.
•
Contact your local Johnson Controls
Service Center.
Low Battery Voltage
Voltage level of the battery in the control board fell.
Press the
ALARM RESET
button after replacement of
the battery in the control board.
Replace the battery on the PWB.
ELB Trip
Earth leakage breaker for surge arrester was
activated.
Contact your local Johnson Controls
Service Center.
YHAU-C Single Effect Steam-Fired Absorption Chiller
136
Содержание York YHAU-C
Страница 2: ......
Страница 26: ...Figure 6 Fitting tir rollers to the machine YHAU C Single Effect Steam Fired Absorption Chiller 24...
Страница 33: ...Figure 11 Location of rupture disk 31 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 85: ...Figure 37 PLC and touch screen communication wiring 83 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 103: ...Figure 49 Cooling start diagram 101 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 104: ...Figure 50 Cooling stop diagram YHAU C Single Effect Steam Fired Absorption Chiller 102...
Страница 166: ...Figure 73 Steam and drain system YHAU C Single Effect Steam Fired Absorption Chiller 164...
Страница 167: ...Figure 74 Duhring diagram PTX chart F 165 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 168: ...Figure 75 Duhring diagram PTX chart C YHAU C Single Effect Steam Fired Absorption Chiller 166...
Страница 169: ...Figure 76 Specific gravity concentration F 167 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 170: ...Figure 77 Specific gravity concentration C YHAU C Single Effect Steam Fired Absorption Chiller 168...
Страница 178: ...Figure 79 Troubleshooting sequence flow chart YHAU C Single Effect Steam Fired Absorption Chiller 176...