JOHNSON CONTROLS
3
FORM 155.34-CL2
ISSUE DATE: 12/10/2017
E. Vacuum Pump
1. Vacuum pump is charged with the correct amount
of lubricant oil. ..........................................................
2. Vacuum pump motor rotation is correct. .................
F. Evacuate Nitrogen Charge
1. Remove the plug in the purge line. .........................
2. Release the nitrogen gas until the generator com-
pound gauge indicates approximately 0.725 PSI. ....
3. Re-install the plug in the purge line. ........................
4. Navigate to the Setting screen on the Control Pan-
el. .............................................................................
5. Press the purge pump
ON
button. ...........................
6. Check the oil level in the purge pump. .....................
7. Using the vacuum pump, evacuate the nitrogen
gas until the generator compound gauge indicates
approximately -14.5 PSI ..........................................
8. Close all open manual valves. .................................
9. Press the purge pump
OFF
button. .........................
10. Turn the power switch (MCCB) off. ..........................
11. Replace or add oil to the purge pump. .....................
G. Panel Checks
1. Thermal relays conform to the factory inspection
sheet. ......................................................................
2. Interlock and answerback signal(s) for the follow-
ing are available:
a. Chilled water pump ..............................................
b. Cooling water pump .............................................
3. Indicators on the Control Panel are correct....
4. The temperature setting parameters for capac-
ity control are correct.............................................
5. Date and time reflect local time zone.....................
6. The rotation direction is correct for the following:
a. Solution circulation pump ....................................
b. Solution spray pump ............................................
c. Refrigerant pump .................................................
7. The water flow suspension switch works properly....
NOTES:
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
107
YHAU-C Single Effect Steam-Fired Absorption Chiller
Содержание York YHAU-C
Страница 2: ......
Страница 26: ...Figure 6 Fitting tir rollers to the machine YHAU C Single Effect Steam Fired Absorption Chiller 24...
Страница 33: ...Figure 11 Location of rupture disk 31 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 85: ...Figure 37 PLC and touch screen communication wiring 83 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 103: ...Figure 49 Cooling start diagram 101 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 104: ...Figure 50 Cooling stop diagram YHAU C Single Effect Steam Fired Absorption Chiller 102...
Страница 166: ...Figure 73 Steam and drain system YHAU C Single Effect Steam Fired Absorption Chiller 164...
Страница 167: ...Figure 74 Duhring diagram PTX chart F 165 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 168: ...Figure 75 Duhring diagram PTX chart C YHAU C Single Effect Steam Fired Absorption Chiller 166...
Страница 169: ...Figure 76 Specific gravity concentration F 167 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 170: ...Figure 77 Specific gravity concentration C YHAU C Single Effect Steam Fired Absorption Chiller 168...
Страница 178: ...Figure 79 Troubleshooting sequence flow chart YHAU C Single Effect Steam Fired Absorption Chiller 176...