After the review is complete, start the chiller.
1. Navigate to the Control Panel Main screen.
2. Press the
OPER.
button on the Control Panel to start the chiller. To start the chiller from a
remote location, enter the remote start signal.
When the chiller starts, the following occurs:
• The solution pump and the refrigerant pump start.
• The steam condensate control valve and the steam shut-off valve (option) open.
• The Control V Low Hold lamp lights. The low opening of the steam condensate control valve is
held for approximately 10 minutes.
• After 10 minutes, the steam condensate control valve is automatically controlled according to the
chilled water outlet temperature.
Stopping the chiller
1. Navigate to the Control Panel Main screen.
2. Press the
STOP
button on the Control Panel. To stop the chiller from a remote location, enter
the remote stop signal.
When the chiller stops, the following occurs:
• The steam condensate control valve and the steam shut-off valve (option) close.
• The dilution operation starts and continues for 7 minutes to 30 minutes.
Note:
During the dilution operation, the solution pumps and the refrigerant pump operate.
• When the dilution operation is complete, the solution pumps and the refrigerant pump stop.
• Then, the chilled water pump, cooling water pump, and cooling tower stop.
YHAU-C Single Effect Steam-Fired Absorption Chiller
100
Содержание York YHAU-C
Страница 2: ......
Страница 26: ...Figure 6 Fitting tir rollers to the machine YHAU C Single Effect Steam Fired Absorption Chiller 24...
Страница 33: ...Figure 11 Location of rupture disk 31 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 85: ...Figure 37 PLC and touch screen communication wiring 83 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 103: ...Figure 49 Cooling start diagram 101 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 104: ...Figure 50 Cooling stop diagram YHAU C Single Effect Steam Fired Absorption Chiller 102...
Страница 166: ...Figure 73 Steam and drain system YHAU C Single Effect Steam Fired Absorption Chiller 164...
Страница 167: ...Figure 74 Duhring diagram PTX chart F 165 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 168: ...Figure 75 Duhring diagram PTX chart C YHAU C Single Effect Steam Fired Absorption Chiller 166...
Страница 169: ...Figure 76 Specific gravity concentration F 167 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 170: ...Figure 77 Specific gravity concentration C YHAU C Single Effect Steam Fired Absorption Chiller 168...
Страница 178: ...Figure 79 Troubleshooting sequence flow chart YHAU C Single Effect Steam Fired Absorption Chiller 176...