Table 23: Failure list
Button label (failure name)
Operation at failure
occurrence
Cause
Chilled W. Time Out (Chilled Water
Time Out)
Chilled water pump operation interlock and/or chilled
water suspension relay was not established in a set
time while start-up.
Cooling W. Time Out (Cooling Water
Time Out)
Not start
Cooling water pump operation interlock was not
established in a set time while start-up.
Operation interlock
Operation interlock was not established during
solution pump automatic operation.
CW Pump Interlock (Cooling Water
Pump Interlock)
Cooling water pump interlock was not established
during cooling water pump operation command
output.
Monitor. Interlock (Monitoring
Interlock)
Stop after dilution
Constantly monitoring interlock (seismoscope, high
room temperature signal, etc) was not established.
Chilled W. Suspension (Chilled Water
Suspension)
Chilled water flow suspension had been detected
continuously during solution pump automatic
operation.
Chilled W. Overcooled (Chilled Water
Overcool)
Chilled water outlet temperature fell down abnormally
during cooling operation.
Refrigerant Overcooled
Stop without dilution
Refrigerant temperature fell down abnormally during
cooling operation, and then refrigerant overcool relay
was activated.
Low Cool. W. Inlet Temp. (Low
Cooling Water Inlet Temperature).
Stop after dilution
Cooling water inlet temperature had been kept at its
lower limit or lower for 30 minutes or longer during
cooling operation.
Cooling W. Suspension (Cooling
Water Suspension) (Option)
Stop without dilution
Cooling water suspension had been detected
continuously during solution pump automatic
operation while cooling operation.
Control Sensor Abnormal
Temperature sensor and/or pressure sensor detected
abnormal value due to disconnection, short circuit,
power outage and so forth.
CPU Abnormal
Stop after dilution
CPU was judged to be abnormal.
Sol. Circu. P. Abnormal (Solution
Circulation Pump Abnormal)
Solution circulation pump thermal relay, or overheat
switch was activated.
Sol. Spray P. Abnormal (Solution
Spray Pump Abnormal)
Solution spray pump thermal relay, or overheat switch
was activated.
Refrigerant P. Abnormal (Refrigerant
Pump Abnormal)
Stop without dilution
Refrigerant pump thermal relay, or overheat switch
was activated.
Gen. High Temp. (Generator High
Temperature)
Generator solution temperature rose up abnormally.
Chiller High Press. (Chiller High
Pressure)
Stop after dilution
Chiller internal pressure rose abnormally
YHAU-C Single Effect Steam-Fired Absorption Chiller
134
Содержание York YHAU-C
Страница 2: ......
Страница 26: ...Figure 6 Fitting tir rollers to the machine YHAU C Single Effect Steam Fired Absorption Chiller 24...
Страница 33: ...Figure 11 Location of rupture disk 31 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 85: ...Figure 37 PLC and touch screen communication wiring 83 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 103: ...Figure 49 Cooling start diagram 101 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 104: ...Figure 50 Cooling stop diagram YHAU C Single Effect Steam Fired Absorption Chiller 102...
Страница 166: ...Figure 73 Steam and drain system YHAU C Single Effect Steam Fired Absorption Chiller 164...
Страница 167: ...Figure 74 Duhring diagram PTX chart F 165 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 168: ...Figure 75 Duhring diagram PTX chart C YHAU C Single Effect Steam Fired Absorption Chiller 166...
Страница 169: ...Figure 76 Specific gravity concentration F 167 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 170: ...Figure 77 Specific gravity concentration C YHAU C Single Effect Steam Fired Absorption Chiller 168...
Страница 178: ...Figure 79 Troubleshooting sequence flow chart YHAU C Single Effect Steam Fired Absorption Chiller 176...