JOHNSON CONTROLS
7
FORM 155.34-CL2
ISSUE DATE: 12/10/2017
COMMISSIONING DATA SHEET (2/2) (STEAM SINGLE-EFFECT ABSORPTION CHILLER)
User:
Model:
MFG.No.:
User's machine code:
Running Data
Date:
Measured by
Specification
Standard
:
:
:
Steam
Steam condensate
control valve position
%
Control panel
Steam primary pressure
Pressure gauge
≤156 PSIG
Steam secondary pres-
sure
Pressure gauge
Steam temperature
°F
Thermometer
≤347°F
Drain outlet (back)
pressure
Pressure gauge
Drain temperature
°F
Thermometer
≤203°F
Steam consumption
Flow meter
Chilled
Water
Inlet temperature
°F
Control panel
Outlet temperature
°F
Control panel
Inlet pressure
PSIG
Pressure gauge
Outlet pressure
PSIG
Pressure gauge
[3] Pressure drop
PSIG DPM or calculation
[4]
[1] Flow rate
ft3/h
FM or calculation
[2]
Cooling
Water
Inlet temperature
°F
Control panel
68 ~ 89.6°F
Outlet temperature
°F
Control panel
68 ~ 89.6°F
Inlet pressure
PSIG
Pressure gauge
Outlet pressure
PSIG
Pressure gauge
[7] Pressure drop
PSIG
DPG or calculation
[8]
[5] Flow rate
ft3/h
FM or calculation
[6]
Absorption
Cycle
Generator press. (Gauge)
PSIG
Compound gauge
Generator press. (Sensor)
mmHg
Control panel
Generator
temperature
°F
Control panel
≤329°F
Generator
concentration
%
Control panel
Absorber temperature
°F
Control panel
Refrigerant temperature
°F
Control panel
Liquid
Level
Generator
-
Level gauge
Absorber
-
Level gauge
Evaporator (Lower)
-
Level gauge
Evaporator (Upper)
-
Level gauge
NOTES:
Operating hours hours
Number of purge times times
Fill out each specification pressure drop according to the factory inspection report (actual value).
If differential pressure gauge (DPG) is not available, calculate each pressure drop.
If flow meter (FM) is not available, calculate each flow rate as below.
[1] = [2] x √[3]/[4] [5]=[6] x √[7]/[8]
LD20020
Same
Height
Waterbox
OUT
P
P
IN
111
YHAU-C Single Effect Steam-Fired Absorption Chiller
Содержание York YHAU-C
Страница 2: ......
Страница 26: ...Figure 6 Fitting tir rollers to the machine YHAU C Single Effect Steam Fired Absorption Chiller 24...
Страница 33: ...Figure 11 Location of rupture disk 31 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 85: ...Figure 37 PLC and touch screen communication wiring 83 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 103: ...Figure 49 Cooling start diagram 101 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 104: ...Figure 50 Cooling stop diagram YHAU C Single Effect Steam Fired Absorption Chiller 102...
Страница 166: ...Figure 73 Steam and drain system YHAU C Single Effect Steam Fired Absorption Chiller 164...
Страница 167: ...Figure 74 Duhring diagram PTX chart F 165 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 168: ...Figure 75 Duhring diagram PTX chart C YHAU C Single Effect Steam Fired Absorption Chiller 166...
Страница 169: ...Figure 76 Specific gravity concentration F 167 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 170: ...Figure 77 Specific gravity concentration C YHAU C Single Effect Steam Fired Absorption Chiller 168...
Страница 178: ...Figure 79 Troubleshooting sequence flow chart YHAU C Single Effect Steam Fired Absorption Chiller 176...