Table 14: Ethernet interface specification
Item
Specification
Blink
Data sending/receiving
Active
(Green)
No light
No data sending/receiving
Blink
Data sending/receiving through
10 BASE-T / 100 BASE-TX
LED function
Link
(Green)
No light
No connection or successor job failure
Communication specification
Table 15: Communication specifications
Communication protocol
Modbus TCP
Communication path type
10 BASE-T / 100 BASE-TX
IP address
(No. 1) 192.168.1.1, (No.2) 192.168.1.2, (No. 3) 192.168.1.3
Subnet mask
255.255.255.0
Read Command
(Digital Signal) 01/Read Coil
(Analog Signal) 03/Read Holding Register
Function code
Write Command
(Digital Signal) 05/Force Single Coil
Communication data
Table 16: Read command
Item
Display
Unit
Address
Content
1
Set Point
46.4
°F
00001
0050~1000 unit, 1 unit=0.1°F
2
Automatic stop temp.
(thermo-off temp)
41
°F
00003
0040~1000 unit, 1 unit=0.1°F
Set value
3
Temp. difference of
Automatic start/stop control
41
°F
00005
0001~1000 unit, 1 unit=0.1°F
4
Operation condition
0 or 1
-
00021
0:STOP, 1:COOLING OPERATION
5 Local/remote mode condition 0 or 1
-
01001
0:LOCAL, 1:REMOTE
6
Solution pump condition
0 or 1
-
01003
0:STOP, 1:OPERATION
7
Refrigerant pump condition
0 or 1
-
01005
0:STOP, 1:OPERATION
8
Load limit condition
0 or 1
-
01009
0:NORMALLY OPERATION
1:LOAD LIMIT OPERATION
9 Control manipulated variable
100
%
00023
-0100~1100 unit, 1 unit=0.1%
10
Failure signal
0 or 1
-
01011
0:NORMAL OPERATION
1:FAILURE OCCUR
Operation condition
11
Alarm signal
0 or 1
-
01013
0:NORMAL OPERATION
1:ALARM OCCUR
12
Chilled water inlet temp.
55
°F
00083
0001~4000 unit, 1 unit=0.1°F
13
Chilled water outlet temp.
46.4
°F
00085
0001~4000 unit, 1 unit=0.1°F
14
Refrigerant temp
at evaporator
42.8
°F
00087
0001~4000 unit, 1 unit=0.1°F
15
Cooling water inlet temp.
87
°F
00089
0001~4000 unit, 1 unit=0.1°F
16
Cooling water outlet temp.
98.6
°F
00091
0001~4000 unit, 1 unit=0.1°F
17
Absorber solution temp.
100.4
°F
00093
0001~4000 unit, 1 unit=0.1°F
18
Generator temp.
194
°F
00095
0001~4000 unit, 1 unit=0.1°F
19
Generator pressure
176
mmHg
00101 0001~4000 unit, 1 unit=0.1 mmHg
Measurement value
20
Purge tank pressure
15
mmHg
00103 0001~4000 unit, 1 unit=0.1 mmHg
91
YHAU-C Single Effect Steam-Fired Absorption Chiller
Содержание York YHAU-C
Страница 2: ......
Страница 26: ...Figure 6 Fitting tir rollers to the machine YHAU C Single Effect Steam Fired Absorption Chiller 24...
Страница 33: ...Figure 11 Location of rupture disk 31 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 85: ...Figure 37 PLC and touch screen communication wiring 83 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 103: ...Figure 49 Cooling start diagram 101 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 104: ...Figure 50 Cooling stop diagram YHAU C Single Effect Steam Fired Absorption Chiller 102...
Страница 166: ...Figure 73 Steam and drain system YHAU C Single Effect Steam Fired Absorption Chiller 164...
Страница 167: ...Figure 74 Duhring diagram PTX chart F 165 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 168: ...Figure 75 Duhring diagram PTX chart C YHAU C Single Effect Steam Fired Absorption Chiller 166...
Страница 169: ...Figure 76 Specific gravity concentration F 167 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 170: ...Figure 77 Specific gravity concentration C YHAU C Single Effect Steam Fired Absorption Chiller 168...
Страница 178: ...Figure 79 Troubleshooting sequence flow chart YHAU C Single Effect Steam Fired Absorption Chiller 176...