Maintenance
When inspecting and maintaining the absorption chiller, observe the following items:
• Never splash water over the electrical parts installed to the control panel and absorption chiller.
• Do not change the set values of the control devices and safety switches without permission.
• Do not turn the internal cycle control valve of the absorption chiller without permission.
• When replacing the oil in the vacuum pump, turn OFF the main circuit breaker (MCCB) in the
control panel.
Valve inspection
The chiller is equipped with a refrigerant manual blow valve (V8) that blows refrigerant from the
refrigerant tank to the absorber directly. See Figure 69.
The valve must not be tampered with or the settings changed. An exception is daily maintenance
and inspection.
WARNING
During service and maintenance work, turn OFF the main circuit breaker (MCCB) and fully close the
main valve of the steam line. Failure to do so can cause electric shock and burn.
CAUTION
Contact your local Johnson Controls Service Office for inspection and maintenance of the machine.
Improper inspection and maintenance can cause a machine problem and also injure workers.
Solenoid valves
The absorption chiller is equipped with the following solenoid valves.
Table 26: Solenoid valves
Solenoid valve name
Symbol
Function
Purge solenoid valve (1)
SV1
Purge solenoid valve (2)
SV2
Close vacuum pump piping
Refrigerant blow solenoid valve
SV3
Close automatic refrigerant blow piping
Pump shut off valves
The chiller is equipped with the pump shut off valves shown in Figure 69 and Figure 70. They are
used for inspection of the pumps.
If the absorption chiller is operated with incorrect valve settings, the pump can be damaged. Do not
tamper with the valves.
YHAU-C Single Effect Steam-Fired Absorption Chiller
142
Содержание York YHAU-C
Страница 2: ......
Страница 26: ...Figure 6 Fitting tir rollers to the machine YHAU C Single Effect Steam Fired Absorption Chiller 24...
Страница 33: ...Figure 11 Location of rupture disk 31 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 85: ...Figure 37 PLC and touch screen communication wiring 83 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 103: ...Figure 49 Cooling start diagram 101 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 104: ...Figure 50 Cooling stop diagram YHAU C Single Effect Steam Fired Absorption Chiller 102...
Страница 166: ...Figure 73 Steam and drain system YHAU C Single Effect Steam Fired Absorption Chiller 164...
Страница 167: ...Figure 74 Duhring diagram PTX chart F 165 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 168: ...Figure 75 Duhring diagram PTX chart C YHAU C Single Effect Steam Fired Absorption Chiller 166...
Страница 169: ...Figure 76 Specific gravity concentration F 167 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 170: ...Figure 77 Specific gravity concentration C YHAU C Single Effect Steam Fired Absorption Chiller 168...
Страница 178: ...Figure 79 Troubleshooting sequence flow chart YHAU C Single Effect Steam Fired Absorption Chiller 176...