Technical Data
1590
1572
880
401
252
1095
321
76 VICTAULIC (typ)
ELECTRICAL ACCESS
PANEL
2292 BASE WIDTH
LEFT END
LIQUID OUT
LIQUID IN
VIEW B-B
22 TYP.
100
82
171
BOTTOM OF PANEL
LD10983
DIMENSIONS - YCAL0065 (SI)
Aluminum
Copper
YCAL
Center of Gravity (in.)
YCAL
Center of Gravity (in.)
X
Y
X
Y
0065
1517.6
1140.3
0065
1655.5
1141.1
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in un pre dict able airfl ow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pres sure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;
rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall - 2m; top – no obstructions allowed; distance between adjacent units – 3m.
No more than one adjacent wall may be higher than the unit. 1" nominal defl ection isolators (not shown) will increase overall unit height by
152mm.
NOTE:
All dimensions are in mm unless specifi ed oth er wise.
Содержание YORK YCAL0041EC
Страница 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM1 708 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 57: ...FORM 150 66 NM1 708 57 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM CON T LD13248 FIG 4 CON T CONTROL CIRCUIT DUAL...
Страница 59: ...FORM 150 66 NM1 708 59 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM CON T FIG 5 CON T CONTROL CIRCUIT DUAL LD13260...
Страница 167: ...FORM 150 66 NM1 708 167 JOHNSON CONTROLS NOTES...