RECEIVED DATA (CONTROL DATA)
The Middle Market receives 8 data values from the
ISN. The fi rst 4 are analog values and the last 4 are
digital values. These 8 data values are used as control
parameters when in REMOTE mode. When the unit is
in LOCAL mode, these 8 values are ignored. If the unit
receives no valid ISN transmission for 5 minutes it will
revert back to all local control values. Table 33 lists
the 4 control parameters. These values are found under
feature 54 on the ISN.
ISN CONTROL
TABLE 34 – ISN TRANSMITTED DATA
TRANSMITTED DATA
After receiving a valid transmission from the ISN, the
unit will transmit either operational data or history buffer
data depending on the “History Buffer Request” on
ISN PAGE 10. Data must be transmitted for every ISN
page under feature 54. If there is no value to be sent to
a particular page, a zero will be sent. Tables 34 and 35
show the data values and page listings for this unit.
ISN PAGES listed are ENG PAGE
REFERENCES and must be decoded
to the corresponding PAGE REF
point map related to the communica-
tions protocol type utilized. The latest
point map information is listed on the
Johnson Controls Group Equipment
Integration website.
ISN
CONTROL DATA
PAGE
P03
SETPOINT
99
=
AUTO
P04
LOAD LIMIT STAGE (0,1, 2)
P05
–
P06
–
P07
START/STOP
COMMAND
(0
=
STOP,
1
=
RUN)
P08
—
P09
—
P10
HISTORY
BUFFER
REQUEST
(0 = CURRENT DATA, 1 = LAST HISTORY DATA)
TABLE 33 – ISN RECEIVED DATA
ISN
PAGE
CHARACTER
TYPE
DATA
P11
8-11
Analog
Leaving Chilled
Liquid Temp.
P12
12-15
Analog
Return Chilled
Liquid Temp.
P13
16-19
Analog
----
P14
20-23
Analog
----
P15
24-27
Analog
SYS 1 Suction
Temp. (EEV Only)
P16
28-31
Analog
Ambient Air Temp.
P17
32-35
Analog
SYS 1 Suction
Superheat
(EEV Only)
P18
36-39
Analog
SYS 1 Run Time
(Seconds)
P19
40-43
Analog
SYS 1 Suction
Pressure
P20
44-47
Analog
SYS 1 Discharge
Pressure
P21
48-51
Analog
----
P22
52-55
Analog
----
P23
56-59
Analog
SYS 1 EEV
Output %
(EEV Only)
P24
60-63
Analog
SYS 1
Anti-Recycle Timer
P25
64-67
Analog
Anti-Coincidence
Timer
P26
68-71
Analog
SYS 2 Suction
Temp. (EEV Only)
P27
72-75
Analog
SYS 2 Run Time
(Seconds)
P28
76-79
Analog
SYS 2
Suction Pressure
P29
80-83
Analog
SYS 2
Discharge Pressure
P30
84-87
Analog
----
P31
88-91
Analog
----
P32
92-95
Analog
SYS 2
Suction Superheat
(EEV Only)
P33
96-99
Analog
SYS 2
Anti-Recycle Timer
P34
100-103
Analog
SYS 2 EEV
Output %
(EEV Only)
P35
104-107
Analog
# of Compressors
P36
108
Digital
SYS 1 Alarm
P37
109
Digital
SYS 2 Alarm
Содержание YORK YCAL0041EC
Страница 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM1 708 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 57: ...FORM 150 66 NM1 708 57 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM CON T LD13248 FIG 4 CON T CONTROL CIRCUIT DUAL...
Страница 59: ...FORM 150 66 NM1 708 59 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM CON T FIG 5 CON T CONTROL CIRCUIT DUAL LD13260...
Страница 167: ...FORM 150 66 NM1 708 167 JOHNSON CONTROLS NOTES...