Service and Troubleshooting
PROBLEM
CAUSE
SOLUTION
“MP / HPCO” FAULT
1. Compressor internal motor
1. Verify refrigerant charge is
protector (MP) open.
not low. Verify superheat
setting of °10 - 15°F (5.6° -
8.
3°C).
Verify
correct
com-
pressor
rotation.
Verify
compressor
is
not
over
loaded.
2. External overload tripped.
2. Determine cause and reset.
3. HPCO switch open.
3.
See “High Press. Disch.”
Fault.
4. Defective HPCO switch.
4. Replace HPCO switch.
5. Defective CR relay.
5. Replace relay.
COMPRESSOR(S) WON’T
1. Demand not great enough.
1. No problem. Consult
START
“Installation” Manual to aid
in
understanding
compres-
sor
operation
and
capacity
control.
2. Defective water temperature
2. Compare the display with a
sensor.
thermometer. Should be
within
+/-
2
degrees.
Refer
to Service section for RWT/
LWT temp./voltage table.
3. Contactor/Overload failure.
3. Replace defective part.
4.
Compressor
failure.
4.
Diagnose
cause
of
failure
and
replace.
LACK OF COOLING EFFECT
1. Fouled evaporator surface.
1. Contact the local YORK
Low suction pressure will
service representative.
be
observed.
2. Improper fl ow through the
2. Reduce fl ow to within chiller
evaporator.
design
specs.
See Limita-
tions in Installation section.
3. Low refrigerant charge.
3. Check subcooling and add
Low suction pressure will
charge as needed.
be
observed.
TROUBLESHOOTING (CONT’D)
Содержание YORK YCAL0041EC
Страница 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM1 708 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 57: ...FORM 150 66 NM1 708 57 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM CON T LD13248 FIG 4 CON T CONTROL CIRCUIT DUAL...
Страница 59: ...FORM 150 66 NM1 708 59 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM CON T FIG 5 CON T CONTROL CIRCUIT DUAL LD13260...
Страница 167: ...FORM 150 66 NM1 708 167 JOHNSON CONTROLS NOTES...