JOHNSON CONTROLS
166
FORM 150.66-NM1 (708)
SERIAL COMMUNICATION BINARY INPUT DATA
This data can be read using a BACnet or Modbus network connection and can NOT be modifi ed using this connection.
The Modbus Register Address for these points is 1281 + BI #.
BI
BACNET NAME
BINARY INPUT DESCRIPTION
1
S1_ALARM
SYS 1 ALARM
2
S2_ALARM
SYS 2 ALARM
3
EVAP_HTR
EVAPORATOR HEATER STATUS
4
EVAP_PUMP
EVAPORATOR PUMP STATUS
5
SI_C1_RUN
SYS COMP 1 RUN
6
S2_C1_RUN
SYS 2 COMP 1 RUN
7
S1_LLSV
SYS 1 LIQUID LINE SOLENOID VALVE
8
S1_MODE_SV
SYS 1 MODE SOLENOID VALVE (HP ONLY)
9
S1_HGBV
SYS 1 HOT GAS BYPASS VALVE
10
S1_BHS
BIVALENT HEAT SOURCE (HP ONLY)
11
S1_C2_RUN
SYS 1 COMP 2 RUN
12
S2_C2_RUN
SYS 2 COMP 2 RUN
13
S2_LLSV
SYS 2 LIQUID LINE SOLENOID VALVE
14
S2_MODE_SV
SYS 2 MODE SOLENOID VALVE (HP ONLY)
15
LEAD_SYS
LEAD SYSTEM (0 = SYS 1, 1 = SYS 2)
16
S1_C3_RUN
SYS 1 COMP 3 RUN
17
S2_C3_RUN
SYS 2 COMP 3 RUN
18
CH_LIQ_TYPE
CHILLED LIQUID TYPE (0 = WATER, 1 = GLYCOL)
19
AMB_MODE
AMBIENT CONTROL MODE (O = STD AMB, 1 = LOW AMB)
20
CNTL_MODE
LOCAL / REMOTE CONTROL MODE (0 = LOCAL, 1 = REMOTE)
21
DATA_UNIT
UNITS (0 = IMPERIAL, 1 = SI)
22
AUTO_LL
LEAD / LAG CONTROL MODE (0 = MANUAL, 1 = AUTO)
23
S2_HGBV
SYS 2 HOT GAS BYPASS VALVE
Содержание YORK YCAL0041EC
Страница 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM1 708 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 57: ...FORM 150 66 NM1 708 57 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM CON T LD13248 FIG 4 CON T CONTROL CIRCUIT DUAL...
Страница 59: ...FORM 150 66 NM1 708 59 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM CON T FIG 5 CON T CONTROL CIRCUIT DUAL LD13260...
Страница 167: ...FORM 150 66 NM1 708 167 JOHNSON CONTROLS NOTES...