JOHNSON CONTROLS
52
FORM 150.66-NM1 (708)
Technical Data
SINGLE POINT FIELD SUPPLIED POWER WIRING
(See Fig. 2)
(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused Discon-
nect Switch (optional) or Circuit Breaker (optional)).
ELCTRICAL DATA (ENGLISH)
YCAL0041_ - YCAL0071_
TABLE 10 – ELECTRICAL DATA (ENGLISH)
MODEL
YCAL
VOLT/
60Hz
MCA
1
MIN N/F
DISC
SW
2
D.E. FUSE
CKT. BKR.
5
FIELD WIRING LUGS
6
TERMINAL BLOCK (STD)
FIELD WIRING LUGS
6
NF DISC. SWITCH (OPT)
FIELD WIRING LUGS
6
CIRCUIT BREAKER (OPT)
REC.
MAX
4
REC.
MAX
LUGS/
PHASE
LUG WIRE RANGE
LUGS/
PHASE
LUG WIRE RANGE
LUGS/
PHASE
LUG WIRE RANGE
0041
200
197
250
225
225
225
225
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
230
184
250
200
200
200
200
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
380
107
150
125
125
125
125
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
460
90
100
100
100
100
100
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
575
71
100
80
80
80
80
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
0045
200
199
250
225
225
225
225
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
230
186
250
200
200
200
200
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
380
108
150
125
125
125
125
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
460
91
100
100
100
100
100
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
575
71
100
80
80
80
80
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
0051
200
228
250
250
250
250
250
1
6awg - 500MCM
2
3/0 - 250MCM
2
3/0 - 250MCM
230
212
250
225
250
225
250
1
6awg - 500MCM
2
3/0 - 250MCM
2
3/0 - 250MCM
380
123
150
150
150
150
150
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
460
103
150
110
110
110
110
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
575
81
100
90
90
90
90
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
0055
200
251
400
300
300
300
300
1
6awg - 500MCM
2
3/0 - 250MCM
2
3/0 - 250MCM
230
234
400
250
300
250
300
1
6awg - 500MCM
2
3/0 - 250MCM
2
3/0 - 250MCM
380
136
150
150
150
150
150
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
460
113
150
125
125
125
125
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
575
90
100
100
100
100
100
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
0061
200
278
400
300
300
300
300
1
6awg - 500MCM
1
250MCM - 500MCM
1
250MCM - 500MCM
230
259
400
300
300
300
300
1
6awg - 500MCM
1
250MCM - 500MCM
1
250MCM - 500MCM
380
150
200
175
175
175
175
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
460
124
150
150
150
150
150
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
575
99
150
110
110
110
110
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
0065
200
292
400
350
350
350
350
1
6awg - 500MCM
1
250MCM - 500MCM
1
250MCM - 500MCM
230
272
400
300
300
300
300
1
6awg - 500MCM
1
250MCM - 500MCM
1
250MCM - 500MCM
380
158
200
175
175
175
175
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
460
132
150
150
150
150
150
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
575
104
150
110
125
110
125
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
0071
200
307
400
350
350
*
*
*
*
*
*
*
*
230
286
400
350
300
*
*
*
*
*
*
*
*
380
166
200
175
200
*
*
*
*
*
*
*
*
460
138
150
150
150
*
*
*
*
*
*
*
*
575
109
150
125
125
*
*
*
*
*
*
*
*
* - Chiller not available at time of publication.
Содержание YORK YCAL0041EC
Страница 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM1 708 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 57: ...FORM 150 66 NM1 708 57 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM CON T LD13248 FIG 4 CON T CONTROL CIRCUIT DUAL...
Страница 59: ...FORM 150 66 NM1 708 59 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM CON T FIG 5 CON T CONTROL CIRCUIT DUAL LD13260...
Страница 167: ...FORM 150 66 NM1 708 167 JOHNSON CONTROLS NOTES...