FORM 150.66-NM1 (708)
119
JOHNSON CONTROLS
7
(leaving chilled liquid control)
(return chilled liquid control)
The low limit, high limit, and default values for the keys
under “SETPOINTS” are listed in Table 15.
Pressing the COOLING SETPOINTS a third time will
bring up the display that allows the Maximum EMS-
PWM Temperature Reset to be programmed. This
message is shown below.
The Temp Reset value is the maximum allowable reset
of the temperature setpoint. The setpoint can be
reset
upwards by the use of a contact closure on the PWM
Temp Reset input (CTB1 terminals 13 - 20). The PWM
signal may be applied directly on these terminals from
an Energy Management System or from the Temperature
Reset Option Board.
See page 142 for a detailed
explanation of this feature.
As with the other setpoints, the ↑ (UP) arrow and ↓
(DOWN) arrow keys are used to change the Temp Reset
value. After using the ↑ (UP) and ↓ (DOWN) arrows to
adjust to the desired setpoint, the ENTER/ADV key must
be pressed to enter this number into memory.
SCHEDULE/ADVANCE DAY KEY
The SCHEDULE is a seven day daily schedule that
allows one start/stop time per day. The schedule can be
programmed Monday through Sunday with an alternate
holiday schedule available. If no start/stop times are
programmed, the unit will run on demand, providing the
chiller is not shut off on a unit or system shutdown. The
daily schedule is considered “not programmed” when
the times in the schedule are all zeros (00:00 AM).
To set the schedule, press the SCHEDULE/ADVANCE
DAY
key. The display will immediately show the
following display.
When in leaving chilled liquid temperature control, the
micro will attempt to control the leaving water tempera-
ture within the temperature range of the se or
- the range. In the above example, control will be in the
range of 43 - 47°F.
RETURN CHILLED LIQUID CONTROL
In return chilled liquid control, the range no longer has
a +/- X.X °F, but only a + X.X °F RANGE setpoint.
This indicates that the setpoint is not centered within
the RANGE but could be described as the bottom of
the control range. A listing of the limits and the pro-
grammable values for the COOLING SETPOINTS are
shown in Table 15.
The SETPOINT and RANGE displays just described
were based on LOCAL control. If the unit was pro-
grammed for REMOTE control (under the OPTIONS
key), the above programmed setpoints would have no
effect.
When in return chilled liquid temperature control, the
micro will turn all compressors off at setpoint and will
turn compressors on as return chilled liquid tempera-
ture rises. All compressors will be on at se the
range. If the range equals the temperature drop across
the evaporator when fully loaded, the leaving chilled
liquid temperature will remain near the se or - a
few degrees as the chiller loads and unloads according
to return chilled liquid temperature.
Both LEAVING and RETURN control are described in
detail under the section on CAPACITY CONTROL.
REMOTE SETPOINT CONTROL
Pressing the COOLING SETPOINTS key a second
time will display the remote setpoint and cooling
range. This display automatically updates about every
2 seconds. Notice that these setpoints are not “locally”
programmable, but are controlled by a remote device
such as an ISN control, remote reset option board, or
remote PWM signal. These setpoints would only be valid
if the unit was operating in the REMOTE mode.
The following messages illustrate both leaving
chilled liquid control and return chilled liquid control
respectively.
R E M S E T P = 4 4 . 0 ° F
R A N G E = + / - 2 . 0 ° F
R E M S E T P = 4 4 . 0 ° F
R
A
N
G
E =
+
1
0 . 0
°
F
M A X E M S - P W M R E M O T E
T E M P R E S E T = +
2 0 ° F
S E T P O I N T = 4 5 . 0 ° F
R A N G E = +
1 0 . 0 ° F
M O N S T A R T = 0 0 : 0 0 A M
S
T
O
P = 0
0 : 0
0 A
M
Содержание YORK YCAL0041EC
Страница 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM1 708 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 57: ...FORM 150 66 NM1 708 57 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM CON T LD13248 FIG 4 CON T CONTROL CIRCUIT DUAL...
Страница 59: ...FORM 150 66 NM1 708 59 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM CON T FIG 5 CON T CONTROL CIRCUIT DUAL LD13260...
Страница 167: ...FORM 150 66 NM1 708 167 JOHNSON CONTROLS NOTES...