FORM 150.66-NM1 (708)
155
JOHNSON CONTROLS
9
PROBLEM
CAUSE
SOLUTION
“LOW SUCTION PRESSURE”
4. TXV defective.
4. Replace TXV.
FAULT (CONT’D)
5.
Reduced
fl
ow
of
chilled
5.
Check
GPM
(See “Limita
tions” liquid through the
cooler
in
Installation
section).
Check operation of pump,
clean pump strainer, purge
chilled
liquid
system
of
air.
6. Defective suction pressure
6. Replace transducer/low
transducer/low pressure
pressure switch or faulty
switch
or
wiring.
wiring.
Refer to “Service”
section for pressure/voltage
f
ormula.
7. LLSV defective
7. Replace LLSV
“HIGH DISCHARGE
1. Condenser fans not operating
1. Check fan motor, fuses,
PRESSURE” FAULT
or operating backwards.
and contactors. Assure fan
blows
air
upward.
2. Too much refrigerant.
2. Remove refrigerant.
3. Air in refrigerant system.
3. Evacuate and recharge
system.
4. Defective discharge
4. Replace discharge pressure
pressure
transducer.
transducer.
Refer to Service
section for pressure/voltage
formula.
“LOW LIQUID TEMP”
1. Improperly adjusted leaving
1. Re-program the leaving
FAULT
chilled liquid temp. cutout
chilled liquid temp. cutout.
(glycol
only).
2. Micro panel setpoint/range
2. Re-adjust setpoint/range.
values
improperly
programmed.
3. Chilled liquid fl ow too low.
3. Increase chilled liquid fl ow -
refer to Limitations in Instal-
lation
section.
4. Defective LWT or RWT sensor
4. Compare sensor against a
(assure the sensor is properly
known good temperature
installed in the bottom of the well
sensing device.
Refer to
with a generous amount of heat)
Service section for temp./
conductive
compound).
voltage
table.
CONT’D
TROUBLESHOOTING (CONT’D)
Содержание YORK YCAL0041EC
Страница 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM1 708 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 57: ...FORM 150 66 NM1 708 57 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM CON T LD13248 FIG 4 CON T CONTROL CIRCUIT DUAL...
Страница 59: ...FORM 150 66 NM1 708 59 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM CON T FIG 5 CON T CONTROL CIRCUIT DUAL LD13260...
Страница 167: ...FORM 150 66 NM1 708 167 JOHNSON CONTROLS NOTES...