These messages only appear and are programmable
when EEV is selected as the expansion valve type in the
Service Mode. EEV must only be selected when an EEV
is installed. Superheat is programmable between 10°F
- 15°F. A setpoint of 12°F - 15°F is recommended.
S Y S 1 S U C T S U P E R H E A T
S E T P O I N T = X X . X ° F
S Y S 2 S U C T S U P E R H E A T
S E T P O I N T = X X . X ° F
UNIT TRIP VOLTS
For total chiller high current trip programming on
460VAC chillers:
• Add the sum of all the compressor and fan RLA’s
in the chiller.
• Multiply the sum by 1.25
• Divide by 225A
• The resulting voltage is the value that should be
programmed.
For example, if fan and compressor RLA’s total 180A:
5V x 180A
x 1.25 =
1125VA
= 5.0V
225A 225A
The programmed value will be 5.0V.
When communications is required with a BAS or
OptiView Panel, individual unit IDs are necessary for
communications with specifi c chillers on a single RS-
485 line. ID 0-7 is selectable.
R E M O T E U N I T I D
P R O G R A M M E D = X