Technical Data
OPERATIONAL LIMITATIONS (ENGLISH)
VOLTAGE LIMITATIONS
The following voltage limitations are absolute and opera-
tion beyond these limitations may cause serious damage
to the compressor.
TABLE 3 – VOLTAGE LIMITATIONS
UNIT POWER
MIN.
MAX.
200-3-60
180
220
230-3-60
207
253
380-3-60
355
415
460-3-60
414
506
575-3-60
517
633
Excessive fl ow will cause damage to
the cooler. Do not exceed max. cooler
flow. Special care should be taken
when multiple chillers are fed by a
single pump.
TABLE 2 – TEMPERATURES AND FLOWS
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK Offi ce for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK Offi ce for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
4. For operation at temperatures below 25°F (-3.9°C), the optional Low Ambient Kit will need to be installed on the system.
5. For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be installed on the system.
ENGLISH
YCAL
LEAVING WATER
TEMPERATURE (°F)
COOLER FLOW (GPM)
AIR ON CONDENSER (°F)
MIN
MAX
MIN
MAX
MIN
MAX
0041
40
55
40
200
0
125
0045
40
55
40
200
0
125
0051
40
55
40
200
0
125
0055
40
55
60
300
0
125
0061
40
55
60
300
0
125
0065
40
55
60
300
0
125
0071
40
55
60
300
0
125
SECTION 6 - TECHNICAL DATA
Содержание YORK YCAL0041EC
Страница 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM1 708 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 57: ...FORM 150 66 NM1 708 57 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM CON T LD13248 FIG 4 CON T CONTROL CIRCUIT DUAL...
Страница 59: ...FORM 150 66 NM1 708 59 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM CON T FIG 5 CON T CONTROL CIRCUIT DUAL LD13260...
Страница 167: ...FORM 150 66 NM1 708 167 JOHNSON CONTROLS NOTES...