
CAUTION
Risk of Property Damage
Do not apply power to the system before checking all
wiring connections. Improper wiring of this terminal
may cause a short circuit across the 24 VAC power
supply on VMA models. A short circuit may result in a
tripped circuit breaker or blown fuse. If using a trans-
former with a built-in fuse, the transformer may need
to be replaced.
ATTENTION
Risque de dommages matériels
Ne mettez pas l’appareil sous tension avant d’avoir
vérifié toutes les connexions du câblage. Le câblage
inadéquat de cette borne peut causer un court-cir-
cuit sur l’alimentation électrique de 24 V c.a. des VMA
modèles. Un court-circuit peut causer le déclenche-
ment du disjoncteur ou le grillage d’un fusible. Si vous
utilisez un transformateur avec un fusible intégré,
vous pourriez devoir remplacer le transformateur.
To wire the controller, complete the following steps:
1. Terminate wiring according the appropriate
.
2. Wire network sensors and other devices to the
VMA's SA Bus.
3. Wire the FC Bus in a daisy chain.
4. Ensure that the device address DIP switches
are set to the appropriate device address (See
the EOL switch if necessary.
5. Connect the controller to 24 VAC, Class 2 power.
Note:
If you are using the
VMA1615/1626/1628/1630 controller with
the Wireless Field Bus System, refer to the
WNC1800/ZFR182x Pro Series Wireless Field Bus
System Bulletin (LIT-12012320
) or the
ZFR Series
Wireless Field Bus System Bulletin (LIT-12011336
).
Terminal wiring guidelines,
functions, ratings, and
requirements
Input and Output wiring guidelines
See Table 3 for information about the functions,
ratings, and requirements for the input and output
terminals, and for wire sizes and cable lengths
guidelines.
In addition, observe the following guidelines when
wiring inputs and outputs:
• Run all low-voltage wiring and cables separate
from high-voltage wiring.
• All input and output cables, regardless of wire
size or number of wires, should consist of twisted,
insulated, and stranded copper wires.
• Shielded cable is not required for input or output
cables but is recommended for input and output
cables that are exposed to high electromagnetic
or radio frequency noise.
• Cable runs of less than 30 m (100 ft) typically do
not require an offset in the input/output software
setup.
• Cable runs over 30 m (100 ft) may require an
offset in the input/output software setup.
VMA1930 VAV Controller Installation Guide
8