6.  Push down and hold the Manual Override

button (see 

VMA1930 physical features

) and

turn the controller coupler until it contacts the

mechanical end-stop at either the full-closed

(90° boxes) or full-open (45° and 60° boxes)

position.

7.  If the damper for a 90° box closes CCW, rotate

the coupler to the CCW mechanical limit. If

the damper for a 90° box closes CW, rotate

the coupler to the CW mechanical limit. The

open end-stop is automatically set for 90°

boxes. For 45° and 60° boxes, hard stops must

be provided at both full-closed and full-open

damper positions. By installing the controller at

the full-open position, the controller provides

the open stop for 45° and 60° boxes. The closed

damper seal provides the full-closed stop.

Note: 

The integrated actuator has a

stroke time of 60 seconds for 90° of travel.

The stroke time is the amount of time

(in seconds) that it takes the actuator

to move from the fully closed to fully

opened position or from fully open to fully

closed position. For proper operation, the

actuator stroke time must be configured

in the CCT application based on the actual

time it takes the actuator to drive the

damper. The default setting is 60 seconds

(for 90° VAV boxes). For 45° and 60° VAV

boxes, the actuator stroke time must be

adjusted. Refer to 

Controller Tool Help

(LIT-12011147)

 for instructions on setting

the actuator stroke time in the application.

8.  All models are compact in size and can be

easily installed on VAV boxes. The models have

either a round shaft up to 13 mm in diameter

or a 10 mm square shaft. Tighten the square

coupler bolt to the shaft using an 8 mm (5/16

in.) wrench or 10 mm (3/8 in.) 12-point socket.

Tighten to 10.5 to 11.5 N·m (95 to 105 lb·in).

9.  (

Skip this step if you are installing the

VMA1626 model

) Loop the pneumatic tubing

(supplied by field personnel) to include a

trap for condensation. Attach the needed

length of tubing (supplied and installed by

field personnel) to the dual port fitting on the

controller and the other ends of the tubing

to the pressure transducer in the VAV box

application.

Note: 

 The controller uses a digital non-

flow pressure sensor with bidirectional

flow operation. You can connect the high-

and low-pressure DP tubes to either

barbed fitting on the controller. You do not

need to make a specific high- or low-side

connection when you attach the tubing to

the barbed fittings on the controller.

10.  Push the Manual Override button, and turn the

actuator coupling manually to ensure that the

actuator can rotate from full-closed to full-open

positions without binding.

11.  Complete the mounting by rotating the damper

to the full-open position.

 CAUTION

Risk of Property Damage

Rotate the damper to the full-open position before

starting the air handler. Failure to rotate the damper to

the full-open position may result in damage to the VAV

box or ductwork when the air handler is started.

 ATTENTION

Risque de dégâts matériels

Faire pivoter le registre pour le placer en position

d'ouverture complète avant de démarrer l'unité de

traitement d'air. Le non-respect de cette directive

risque d'endommager le caisson de l'unité à volume

d'air variable (VAV) ou le réseau de conduites au dé-

marrage de l'unité de traitement d'air.

Wiring

 CAUTION

Risk of Electric Shock

Disconnect the power supply before making electrical

connections to avoid electric shock.

VMA1930 VAV Controller Installation Guide

5

Содержание VMA1930

Страница 1: ...ence when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction m...

Страница 2: ...Table 3 5 Dual Port Fitting 6 Manual Override Button see Mounting for information about using manual override Button 7 Controller Coupler see Mounting for information about using the controller couple...

Страница 3: ...0mA Analog Input Resistive Mode 0 2k ohm RTD 1k NI Johnson Controls 1k PT A998 SI NTC 10k Type L 2 252k Type 2 Binary Input Dry Contact Maintained Mode 3 Binary Output BO 24 VAC Triac 3 Configurable O...

Страница 4: ...ller so that the enclosure walls do not obstruct cover removal or ventilation through the controller Mount the controller so that the power transformer and other devices do not radiate excessive heat...

Страница 5: ...ing an 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point socket Tighten to 10 5 to 11 5 N m 95 to 105 lb in 9 Skip this step if you are installing the VMA1626 model Loop the pneumatic tubing supplied by fi...

Страница 6: ...port Benefits of daisy chained networks are that they require less physical wiring and new devices can be added easily to the network In a star network each VMA1930 controller is connected by Ethernet...

Страница 7: ...inal block is a gray removable 2 terminal plug that fits into a board mounted jack on the upper left of the VMA controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM te...

Страница 8: ...dress See Setting the controller number Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1615 1626 1628 1630 controller with the...

Страница 9: ...1k Platinum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 4...

Страница 10: ...s Table 4 Cable length guidelines Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 2...

Страница 11: ...Communications COM SA Bus Signal Reference and 15 VDC Common SA BUS 2 2 POWER 15 VDC Supply Power for Devices on the SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended No...

Страница 12: ...the figures in this section for the applicable termination diagrams Table 6 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage...

Страница 13: ...uator External Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog...

Страница 14: ...ing the controller Setting the controller number Each controller on a network must have a unique number on the subnet where it resides in order to identify it in the Controller Tool for uploading down...

Страница 15: ...tions on the input and output terminals including the integrated DPT It assumes all Universal Inputs UIs are Nickel temperature sensors All Configurable Outputs COs are treated as Binary Outputs BOs w...

Страница 16: ...uses to trip make sure that the power connections on theVMA1930 are not reversed The most common cause of this problem is when the 24 VAC power supply on the VMA1930 is reversed but not reversed on a...

Страница 17: ...Transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not shared between multiple pieces of equipment Configurable output analog mode is invalid 0 1...

Страница 18: ...cm 30 in Primary Leads and 76 2 cm 30 in Secondary Leads Class 2 Y65A13 0 Transformer 120 VAC Primary to 24 VAC Secondary 40 VA Foot Mount Y65AS 20 32 cm 8 in Primary Leads and 76 2 cm 30 in Secondar...

Страница 19: ...een 001 and 999 Communications Bus Two Ethernet ports 10 100 Mbps 8 pin RJ 45 connector SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended from the VMA controller for netw...

Страница 20: ...nced Application Controller B AAC based on the ANSI ASHRAE 135 2016 The performance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these sp...

Отзывы: