Maximum cable length versus load
current

Use Figure 7 to estimate the maximum cable length

relative to the wire size and the load current (in mA)

when wiring inputs and outputs.

Figure  7: Maximum Wire Length by Current and

Wire Size

Communications bus and supply
power wiring guidelines

 provides information about terminal block

functions, ratings, and requirements..
In addition, observe these guidelines when wiring

the SA Buses and supply power:
• Run 

all

 low-voltage wiring and cables separate

from high-voltage wiring.

• All SA Bus cables, regardless of wire size, should

be twisted, insulated, stranded copper wire.

• Shielded cable is strongly recommended for all SA

Bus cables.

• Refer to the 

 MS/TP Communications Bus

Technical Bulletin (LIT-12011034)

 for detailed

information regarding wire size and cable length

requirements for SA Buses.

Communication bus and supply power terminal blocks, ratings, and requirements

Table  5: Communication bus and supply power terminal blocks, functions, ratings, requirements, and

cables

Terminal block/Port label

Terminal labels

Function, electrical ratings/

Requirements

Recommended cable type

1

1

+
-

SA Bus Communications

COM

SA Bus Signal Reference and 15 VDC

Common

SA BUS

2

2

POWER

15 VDC Supply Power for Devices on the

SA Bus

0.6 mm (22 AWG) stranded, 4-wire

(2 twisted-pairs), shielded cable

recommended

Note: 

The + and - wires are one

twisted pair, and the COM and

SA PWR wires are the second

twisted pair.

SENSOR

SENSOR

RJ-12 6-Position Modular Port provides

SA Bus Communications
SA Bus provides 15 VDC Power for:
NS Series Sensors
MAP Gateway 4.2 or above
Bluetooth Commissioning Converter

(BTCVT)

3

3

DIS1710 Local Controller Display
VAV Balancing Tool

24 AWG 3-pair CAT 3 Cable <30.5 m

(100 ft)

ETH1 and ETH2

ETH1 and ETH2

Connect to BACnet/IP Network

Ethernet ports; 10/100 Mbps; 8-pin

RJ-45 connector

HOT

24 VAC Power Supply - Hot

Supplies 20–30 VAC (Nominal 24 VAC)

24~

COM

24 VAC Power Supply Common

The terminal is isolated from the FC bus

common.

0.8 mm to 1.0 mm
(20 to 18 AWG) 2-wire

1

To determine wire size and cable lengths for cables other than the recommended cables, see Table 4.

2

The SA bus wiring recommendations are for MS/TP Bus communications at 38.4k baud. For more information, refer to the 

MS/TP

Communications BusTechnical Bulletin (LIT-12011034)

.

3

The MAP Gateway serves as a replacement for the BTCVT, which is no longer available for purchase, but continues to be supported.

VMA1930 VAV Controller Installation Guide

11

Содержание VMA1930

Страница 1: ...ence when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction m...

Страница 2: ...Table 3 5 Dual Port Fitting 6 Manual Override Button see Mounting for information about using manual override Button 7 Controller Coupler see Mounting for information about using the controller couple...

Страница 3: ...0mA Analog Input Resistive Mode 0 2k ohm RTD 1k NI Johnson Controls 1k PT A998 SI NTC 10k Type L 2 252k Type 2 Binary Input Dry Contact Maintained Mode 3 Binary Output BO 24 VAC Triac 3 Configurable O...

Страница 4: ...ller so that the enclosure walls do not obstruct cover removal or ventilation through the controller Mount the controller so that the power transformer and other devices do not radiate excessive heat...

Страница 5: ...ing an 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point socket Tighten to 10 5 to 11 5 N m 95 to 105 lb in 9 Skip this step if you are installing the VMA1626 model Loop the pneumatic tubing supplied by fi...

Страница 6: ...port Benefits of daisy chained networks are that they require less physical wiring and new devices can be added easily to the network In a star network each VMA1930 controller is connected by Ethernet...

Страница 7: ...inal block is a gray removable 2 terminal plug that fits into a board mounted jack on the upper left of the VMA controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM te...

Страница 8: ...dress See Setting the controller number Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1615 1626 1628 1630 controller with the...

Страница 9: ...1k Platinum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 4...

Страница 10: ...s Table 4 Cable length guidelines Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 2...

Страница 11: ...Communications COM SA Bus Signal Reference and 15 VDC Common SA BUS 2 2 POWER 15 VDC Supply Power for Devices on the SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended No...

Страница 12: ...the figures in this section for the applicable termination diagrams Table 6 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage...

Страница 13: ...uator External Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog...

Страница 14: ...ing the controller Setting the controller number Each controller on a network must have a unique number on the subnet where it resides in order to identify it in the Controller Tool for uploading down...

Страница 15: ...tions on the input and output terminals including the integrated DPT It assumes all Universal Inputs UIs are Nickel temperature sensors All Configurable Outputs COs are treated as Binary Outputs BOs w...

Страница 16: ...uses to trip make sure that the power connections on theVMA1930 are not reversed The most common cause of this problem is when the 24 VAC power supply on the VMA1930 is reversed but not reversed on a...

Страница 17: ...Transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not shared between multiple pieces of equipment Configurable output analog mode is invalid 0 1...

Страница 18: ...cm 30 in Primary Leads and 76 2 cm 30 in Secondary Leads Class 2 Y65A13 0 Transformer 120 VAC Primary to 24 VAC Secondary 40 VA Foot Mount Y65AS 20 32 cm 8 in Primary Leads and 76 2 cm 30 in Secondar...

Страница 19: ...een 001 and 999 Communications Bus Two Ethernet ports 10 100 Mbps 8 pin RJ 45 connector SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended from the VMA controller for netw...

Страница 20: ...nced Application Controller B AAC based on the ANSI ASHRAE 135 2016 The performance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these sp...

Отзывы: