General troubleshooting

Table  8: Troubleshooting

Problem

Possible cause and correction

Verification

Controller is OFF.

Transformer has tripped:

Power is at Primary of Transformer, 0V at

Secondary.

Breaker/Fuse has tripped:

Power is at Primary of Transformer, 24V at

Secondary, 0V at Fuse/Breaker.

Cause:

1. Transformer is shorted.
2. 24 VAC powered sensor is not

wired with the same polarity as the

controller.

3. SA Bus device is not wired with the

same polarity as the controller.

Correction:

1. Ensure polarity of ~24 V COM / ICOM /

+ 15VCOM/SA BUS COM on the

controller, auxiliary devices, and I/O is

the same.

2. Ensure OUT1-OUT3 terminals of binary

outputs are not connected to ~24

VAC COM, and verify that OCOM1-

OCOM3 are not connected to ~24 VAC

HOT (these terminals are internally

sourced).

3. Verify the short circuit has been

resolved with an ohm-meter.

4. Reset the breaker/fuse or replace the

transformer.

Note: 

When replacing the

transformer, it is recommended to

replace with a model that utilizes a

resettable circuit breaker. A circuit

breaker makes solving wiring

problems easier.

1. Disconnect the Secondary of the 24

VAC transformer.

2. Use an ohm-meter to measure

between ~24 V HOT and COM; there

must be no short circuit.

Note: 

Some installations require

the Secondary of the Transformer

to be Earth Grounded. If this is

the case, verify that the Earth

Ground connection is valid and not

shared between multiple pieces of

equipment.

Configurable output - analog mode is

invalid

:

0–10 V output is set to 10–100%, but 0 V is at

output terminals.

Output is in protection mode

, a state the

analog portion of the configurable output

goes into when it detects a wiring problem.

The analog output is set to 0% regardless

of the command whenever a wiring fault is

detected.

Cause:

There is a power polarity mismatch between

the connected device and the configurable

output.

Correction:

Ensure polarities of ~24 V COM/OCOM

match and that the connected end device

uses the same polarity.

1. Measure the output and verify that it

matches the command.

2. Disconnect the connected device

and verify the commanded value is

present.

Configurable output - analog mode is

invalid

:

0–10V output has an undesirable offset of up

to 1 V.

The Common Reference is incorrect.

Cause:

The OCOM terminal is not connected.

Correction:

Connect the OCOM terminal of the

configurable output to the common of the

connected end device.

1. Measure the output and verify that it

matches the command.

2. Disconnect the connected device

and verify the commanded value is

present.

Repair information

If the controller fails to operate within its specifications, replace the unit. For a replacement unit, contact the

nearest Johnson Controls representative.

VMA1930 VAV Controller Installation Guide

17

Содержание VMA1930

Страница 1: ...ence when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction m...

Страница 2: ...Table 3 5 Dual Port Fitting 6 Manual Override Button see Mounting for information about using manual override Button 7 Controller Coupler see Mounting for information about using the controller couple...

Страница 3: ...0mA Analog Input Resistive Mode 0 2k ohm RTD 1k NI Johnson Controls 1k PT A998 SI NTC 10k Type L 2 252k Type 2 Binary Input Dry Contact Maintained Mode 3 Binary Output BO 24 VAC Triac 3 Configurable O...

Страница 4: ...ller so that the enclosure walls do not obstruct cover removal or ventilation through the controller Mount the controller so that the power transformer and other devices do not radiate excessive heat...

Страница 5: ...ing an 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point socket Tighten to 10 5 to 11 5 N m 95 to 105 lb in 9 Skip this step if you are installing the VMA1626 model Loop the pneumatic tubing supplied by fi...

Страница 6: ...port Benefits of daisy chained networks are that they require less physical wiring and new devices can be added easily to the network In a star network each VMA1930 controller is connected by Ethernet...

Страница 7: ...inal block is a gray removable 2 terminal plug that fits into a board mounted jack on the upper left of the VMA controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM te...

Страница 8: ...dress See Setting the controller number Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1615 1626 1628 1630 controller with the...

Страница 9: ...1k Platinum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 4...

Страница 10: ...s Table 4 Cable length guidelines Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 2...

Страница 11: ...Communications COM SA Bus Signal Reference and 15 VDC Common SA BUS 2 2 POWER 15 VDC Supply Power for Devices on the SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended No...

Страница 12: ...the figures in this section for the applicable termination diagrams Table 6 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage...

Страница 13: ...uator External Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog...

Страница 14: ...ing the controller Setting the controller number Each controller on a network must have a unique number on the subnet where it resides in order to identify it in the Controller Tool for uploading down...

Страница 15: ...tions on the input and output terminals including the integrated DPT It assumes all Universal Inputs UIs are Nickel temperature sensors All Configurable Outputs COs are treated as Binary Outputs BOs w...

Страница 16: ...uses to trip make sure that the power connections on theVMA1930 are not reversed The most common cause of this problem is when the 24 VAC power supply on the VMA1930 is reversed but not reversed on a...

Страница 17: ...Transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not shared between multiple pieces of equipment Configurable output analog mode is invalid 0 1...

Страница 18: ...cm 30 in Primary Leads and 76 2 cm 30 in Secondary Leads Class 2 Y65A13 0 Transformer 120 VAC Primary to 24 VAC Secondary 40 VA Foot Mount Y65AS 20 32 cm 8 in Primary Leads and 76 2 cm 30 in Secondar...

Страница 19: ...een 001 and 999 Communications Bus Two Ethernet ports 10 100 Mbps 8 pin RJ 45 connector SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended from the VMA controller for netw...

Страница 20: ...nced Application Controller B AAC based on the ANSI ASHRAE 135 2016 The performance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these sp...

Отзывы: