VMA1930 model information
Table 2: VMA1930 information (including point type counts per model)
Communication Protocol
BACnet/IP
Engines Supported
NAE55, NAE85, ODS
Modular Jacks
6-pin SA Bus with four communicating
sensors
Point Types
Signals Accepted
Number of Points
Universal Input (UI)
Analog Input, Voltage Mode, 0–10 VDC
Analog Input, Current Mode, 4-20mA
Analog Input, Resistive Mode, 0–2k ohm, RTD (1k
NI [Johnson Controls], 1k PT, A998 SI), NTC (10k
Type L, 2.252k Type 2)
Binary Input, Dry Contact Maintained Mode
3
Binary Output (BO)
24 VAC Triac
3
Configurable Output (CO)
Analog Output, Voltage Mode, 0–10 VDC
Binary Output Mode, 24 VAC Triac
2
Integrated Actuator
Internal
1
Differential Pressure Transducer (DPT) Internal
1
Up to 4 NS Series Network Zone Sensors
Zone Sensor Input
On SA Bus
Up to 5 WRZ sensors when using the one-to-
one WRZ-78xx wireless configuration
VMA1930 VAV Controller Installation Guide
3