Johnson Controls VMA1930 Скачать руководство пользователя страница 15

Network Settings

. The number of the controller

can be written in the white squares provided so the

controller number can be more easily seen from a

distance.

Figure  8: Rotary switch for setting controller

numbers

Note: 

The BACnet device ID is calculated

using the value of controller number added to

2000000. A device ID configured in this manner

does not require any configuration from CCT.

Input/Output Wiring Validation

The VMA1930 controllers ship with a default state

that can assist in validating the wiring of the input

and output terminals prior to download of an

application file. When the controller is powered on

in this state, the Fault LED will flash in a pattern of

two quick blinks and then a long pause (see Table

7).
To make use of this feature, ensure the rotary

switches are set to the desired controller number

and wire the input and output terminals. Apply

power to the VMA1930 controller and connect to the

device with either a MAP Gateway or MS-DIS1710-0

Local Display to view the points in the controller.

The VMA1930 controller will report an Operational

status even though there is no true application

loaded. CCT will not be able to commission or

upload the device as a result until a true application

is downloaded. The application name displayed will

be the controller number followed by the model of

the controller and “Default State”.

For example, a VMA1930 controller whose rotary

switches are set to 8 would have the default state

application name of 

8-VMA1930 Default State

.

The default state creates I/O points for all

connections on the input and output terminals,

including the integrated DPT. It assumes all

Universal Inputs (UIs) are Nickel temperature

sensors. All Configurable Outputs (COs) are treated

as Binary Outputs (BOs) with an initial value of

0. The actuator on the VMA1930 will drive to the

50% setting. The default state also takes input

from a Network Sensor at address 199. If there is

no connected Network Sensor, the startup of this

default state will be delayed by 30 seconds as the

controller attempts to establish connection with the

sensor.

Commissioning Field Controllers

To commission the VMA1930 controller, use the

following procedure:

1.  Download the control application to the

controller using the Controller Configuration

Tool (CCT). Refer to the 

Controller Tool Help

(LIT-12011147) 

 and 

Controller Provisioning with

Tools (LIT-12013247)

 .

2.  Commission the VAV Box.

3.  Perform airflow balancing on the VAV box.

Refer to the 

VAV Balancing Tool Technical Bulletin

(LIT-12011087)

.

4.  Perform commissioning checkout procedures.

Refer to the 

Controller Tool Help (LIT-12011147) 

and 

Controller Provisioning with Tools

(LIT-12013247)

.

You commission controllers with the CCT software.

The controller can be connected in one of four

ways; either through NxE Passthru, MAP 4.2+/

BACnet Router (Mobile Access Portal (MAP)

Gateway at version 4.2 or above), through Bluetooth

(using BTCVT), or Direct Ethernet connection to

the controller. Refer to the 

Controller Tool Help

(LIT-12011147) 

 and 

Controller Provisioning with

Tools (LIT-12013247)

 for detailed information about

commissioning field controllers.

Note:

• The Bluetooth connection can be used

to Transfer to Computer (Upload) and

commission the controller, but cannot be

used to Transfer to Device (Download).

VMA1930 VAV Controller Installation Guide

15

Содержание VMA1930

Страница 1: ...ence when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction m...

Страница 2: ...Table 3 5 Dual Port Fitting 6 Manual Override Button see Mounting for information about using manual override Button 7 Controller Coupler see Mounting for information about using the controller couple...

Страница 3: ...0mA Analog Input Resistive Mode 0 2k ohm RTD 1k NI Johnson Controls 1k PT A998 SI NTC 10k Type L 2 252k Type 2 Binary Input Dry Contact Maintained Mode 3 Binary Output BO 24 VAC Triac 3 Configurable O...

Страница 4: ...ller so that the enclosure walls do not obstruct cover removal or ventilation through the controller Mount the controller so that the power transformer and other devices do not radiate excessive heat...

Страница 5: ...ing an 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point socket Tighten to 10 5 to 11 5 N m 95 to 105 lb in 9 Skip this step if you are installing the VMA1626 model Loop the pneumatic tubing supplied by fi...

Страница 6: ...port Benefits of daisy chained networks are that they require less physical wiring and new devices can be added easily to the network In a star network each VMA1930 controller is connected by Ethernet...

Страница 7: ...inal block is a gray removable 2 terminal plug that fits into a board mounted jack on the upper left of the VMA controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM te...

Страница 8: ...dress See Setting the controller number Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1615 1626 1628 1630 controller with the...

Страница 9: ...1k Platinum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 4...

Страница 10: ...s Table 4 Cable length guidelines Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 2...

Страница 11: ...Communications COM SA Bus Signal Reference and 15 VDC Common SA BUS 2 2 POWER 15 VDC Supply Power for Devices on the SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended No...

Страница 12: ...the figures in this section for the applicable termination diagrams Table 6 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage...

Страница 13: ...uator External Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog...

Страница 14: ...ing the controller Setting the controller number Each controller on a network must have a unique number on the subnet where it resides in order to identify it in the Controller Tool for uploading down...

Страница 15: ...tions on the input and output terminals including the integrated DPT It assumes all Universal Inputs UIs are Nickel temperature sensors All Configurable Outputs COs are treated as Binary Outputs BOs w...

Страница 16: ...uses to trip make sure that the power connections on theVMA1930 are not reversed The most common cause of this problem is when the 24 VAC power supply on the VMA1930 is reversed but not reversed on a...

Страница 17: ...Transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not shared between multiple pieces of equipment Configurable output analog mode is invalid 0 1...

Страница 18: ...cm 30 in Primary Leads and 76 2 cm 30 in Secondary Leads Class 2 Y65A13 0 Transformer 120 VAC Primary to 24 VAC Secondary 40 VA Foot Mount Y65AS 20 32 cm 8 in Primary Leads and 76 2 cm 30 in Secondar...

Страница 19: ...een 001 and 999 Communications Bus Two Ethernet ports 10 100 Mbps 8 pin RJ 45 connector SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended from the VMA controller for netw...

Страница 20: ...nced Application Controller B AAC based on the ANSI ASHRAE 135 2016 The performance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these sp...