Table  3: I/O terminal blocks, functions, ratings, requirements, and cables

Terminal block label

Terminal labels Function, ratings, and requirements

To determine wire size and

maximum cable length

Analog Output - Voltage Mode (0–10 VDC)

10 VDC maximum output voltage
10 mA maximum output current
External 1k to 50k ohm load required

See Guideline A in Table 4.

OUT

n

Binary Output 24 VAC Triac

Connects OUT to OCOM when activated.
External Power Source:
30 VAC maximum voltage to load
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current

See Guideline C in Table 4.

Analog Output Signal Common

: All Configurable

Outputs defined as Analog Outputs share a

common, which is isolated from all other commons

except the Binary Input common.

CONFIGURABLE

(Outputs)

OCOM

n

Binary Output Signal Common

: All Configurable

Outputs defined as Binary Outputs are isolated

from all other commons, including other

Configurable Output commons.

Same as (Configurable) 

OUT

n

.

Cable and wire length guidelines

The following table defines cable length guidelines

for the various wire sizes that may be used for

wiring low voltage (<30 V) input and outputs.

Table  4: Cable length guidelines

Guideline

Wire size/Gauge and type

Maximum cable length and

type

Assumptions

1.0 mm (18 AWG) stranded copper

457 m (1,500 ft) twisted wire

0.8 mm (20 AWG) stranded copper

297 m (975 ft) twisted wire

297 m (975 ft) twisted wire

0.6 mm (22 AWG) stranded copper

183 m (600 ft) twisted wire

183 m (600 ft) twisted wire

A

0.5mm (24 AWG) stranded copper

107 m (350 ft) twisted wire

107 m (350 ft) twisted wire

100 mV maximum voltage drop
Depending on the cable length

and the connected input or

output device, you may have

to define an offset in the setup

software for the input or output

point.

1.0 mm (18 AWG) stranded copper

229 m (750 ft) twisted wire

0.8 mm (20 AWG) stranded copper

297 m (975 ft) twisted wire

137 m (450 ft) twisted wire

0.6 mm (22 AWG) stranded copper

183 m (600 ft) twisted wire

91 m (300 ft) twisted wire

B

0.5mm (24 AWG) stranded copper

107 m (350 ft) twisted wire

61 m (200 ft) twisted wire

100 mV maximum voltage drop
Depending on the cable length

and the connected input or

output device, you may have

to define an offset in the setup

software for the input or output

point.

C

See 

Maximum cable length versus

load current

 to select wire size/

gauge.
Use stranded copper wire.

See 

Maximum cable length

versus load current

 to determine

cable length.
Use twisted wire cable.

N/A

VMA1930 VAV Controller Installation Guide

10

Содержание VMA1930

Страница 1: ...ence when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction m...

Страница 2: ...Table 3 5 Dual Port Fitting 6 Manual Override Button see Mounting for information about using manual override Button 7 Controller Coupler see Mounting for information about using the controller couple...

Страница 3: ...0mA Analog Input Resistive Mode 0 2k ohm RTD 1k NI Johnson Controls 1k PT A998 SI NTC 10k Type L 2 252k Type 2 Binary Input Dry Contact Maintained Mode 3 Binary Output BO 24 VAC Triac 3 Configurable O...

Страница 4: ...ller so that the enclosure walls do not obstruct cover removal or ventilation through the controller Mount the controller so that the power transformer and other devices do not radiate excessive heat...

Страница 5: ...ing an 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point socket Tighten to 10 5 to 11 5 N m 95 to 105 lb in 9 Skip this step if you are installing the VMA1626 model Loop the pneumatic tubing supplied by fi...

Страница 6: ...port Benefits of daisy chained networks are that they require less physical wiring and new devices can be added easily to the network In a star network each VMA1930 controller is connected by Ethernet...

Страница 7: ...inal block is a gray removable 2 terminal plug that fits into a board mounted jack on the upper left of the VMA controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM te...

Страница 8: ...dress See Setting the controller number Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1615 1626 1628 1630 controller with the...

Страница 9: ...1k Platinum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 4...

Страница 10: ...s Table 4 Cable length guidelines Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 2...

Страница 11: ...Communications COM SA Bus Signal Reference and 15 VDC Common SA BUS 2 2 POWER 15 VDC Supply Power for Devices on the SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended No...

Страница 12: ...the figures in this section for the applicable termination diagrams Table 6 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage...

Страница 13: ...uator External Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog...

Страница 14: ...ing the controller Setting the controller number Each controller on a network must have a unique number on the subnet where it resides in order to identify it in the Controller Tool for uploading down...

Страница 15: ...tions on the input and output terminals including the integrated DPT It assumes all Universal Inputs UIs are Nickel temperature sensors All Configurable Outputs COs are treated as Binary Outputs BOs w...

Страница 16: ...uses to trip make sure that the power connections on theVMA1930 are not reversed The most common cause of this problem is when the 24 VAC power supply on the VMA1930 is reversed but not reversed on a...

Страница 17: ...Transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not shared between multiple pieces of equipment Configurable output analog mode is invalid 0 1...

Страница 18: ...cm 30 in Primary Leads and 76 2 cm 30 in Secondary Leads Class 2 Y65A13 0 Transformer 120 VAC Primary to 24 VAC Secondary 40 VA Foot Mount Y65AS 20 32 cm 8 in Primary Leads and 76 2 cm 30 in Secondar...

Страница 19: ...een 001 and 999 Communications Bus Two Ethernet ports 10 100 Mbps 8 pin RJ 45 connector SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended from the VMA controller for netw...

Страница 20: ...nced Application Controller B AAC based on the ANSI ASHRAE 135 2016 The performance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these sp...

Отзывы: