VMA1930 VAV Controller Installation Guide

Application

The VMA1930 equipment controllers are designed

for Variable Air Volume (VAV) applications that

communicate over BACnet

®

/IP networks. These

Variable Air Volume Modular Assembly (VMA)

controllers feature combinations of an integral

digital pressure sensor (DPT), a damper actuator,

and a 32-bit microprocessor. The controllers' small

package size facilitates quick field installation and

efficient use of space without compromising high-

tech control performance. The VMA1930 controllers

include an integral real-time clock, which enables

the controllers to monitor and control schedules,

calendars, and trends, and operate for extended

periods of time as stand-alone controllers when

offline from the 

 Metasys

®

 system network. These

VMA controllers connect easily to the wired and

wireless network sensors for zone and discharge air

temperature sensing.
The 

 Metasys

 system Field Equipment Controllers

(FEC) family controllers and network sensors

communicate using the BACnet protocol. The

BACnet protocol is a standard for ANSI, ASHRAE,

and the International Standards Organization (ISO)

for building controls. VMA1930 Field Controllers

are BACnet Testing Laboratories (BTL) listed and

certified BACnet Advanced Application Controllers

(B-AACs).

North American emissions
compliance

United States

This equipment has been tested and found to

comply with the limits for a Class A digital device

pursuant to Part 15 of the FCC Rules. These limits

are designed to provide reasonable protection

against harmful interference when this equipment

is operated in a commercial environment. This

equipment generates, uses, and can radiate radio

frequency energy and, if not installed and used in

accordance with the instruction manual, may cause

harmful interference to radio communications.

Operation of this equipment in a residential area

may cause harmful interference, in which case the

users will be required to correct the interference at

their own expense.

Canada

This Class (A) digital apparatus meets all the

requirements of the Canadian Interference-Causing

Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte

toutes les exigences du Règlement sur le matériel

brouilleur du Canada.

Installation

Observe the following guidelines when installing a

VMA1930 controller:
• Transport the controller in the original container

to minimize vibration and shock damage to the

controller.

• Do not drop the controller or subject it to physical

shock.

Parts included

• One VMA1930 controller with removable SA bus

and power terminal blocks

• One installation instructions sheet
• One self-drilling No. 10 x 25 mm (1 in.) screw

Materials and special tools needed

• Several 6 mm (1/4 in.) female spade terminals for

input and output wiring, and crimping tool for

spade mounted terminal blocks

• Small, straight-blade screwdriver for securing

wires in the terminal blocks, can also be used to

adjust controller numbers

• 8 mm (5/16 in.) wrench or 10 mm (3/8 in.) 12-point

socket to tighten the square coupler bolt

• Several shims or washers to mount the VMA
• Power screwdriver, 100 mm (4 in.) extension

socket, punch, drill, and 3.5 mm (9/64 in.) drill bits

to mount the VMA

• Pliers to open and close the damper

*2410143853C*

Part No. 24-10143-853 Rev. C

2019-11-21

(barcode for factory use only)

MS-VMA1930-0

Содержание VMA1930

Страница 1: ...ence when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction m...

Страница 2: ...Table 3 5 Dual Port Fitting 6 Manual Override Button see Mounting for information about using manual override Button 7 Controller Coupler see Mounting for information about using the controller couple...

Страница 3: ...0mA Analog Input Resistive Mode 0 2k ohm RTD 1k NI Johnson Controls 1k PT A998 SI NTC 10k Type L 2 252k Type 2 Binary Input Dry Contact Maintained Mode 3 Binary Output BO 24 VAC Triac 3 Configurable O...

Страница 4: ...ller so that the enclosure walls do not obstruct cover removal or ventilation through the controller Mount the controller so that the power transformer and other devices do not radiate excessive heat...

Страница 5: ...ing an 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point socket Tighten to 10 5 to 11 5 N m 95 to 105 lb in 9 Skip this step if you are installing the VMA1626 model Loop the pneumatic tubing supplied by fi...

Страница 6: ...port Benefits of daisy chained networks are that they require less physical wiring and new devices can be added easily to the network In a star network each VMA1930 controller is connected by Ethernet...

Страница 7: ...inal block is a gray removable 2 terminal plug that fits into a board mounted jack on the upper left of the VMA controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM te...

Страница 8: ...dress See Setting the controller number Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1615 1626 1628 1630 controller with the...

Страница 9: ...1k Platinum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 4...

Страница 10: ...s Table 4 Cable length guidelines Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 2...

Страница 11: ...Communications COM SA Bus Signal Reference and 15 VDC Common SA BUS 2 2 POWER 15 VDC Supply Power for Devices on the SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended No...

Страница 12: ...the figures in this section for the applicable termination diagrams Table 6 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage...

Страница 13: ...uator External Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog...

Страница 14: ...ing the controller Setting the controller number Each controller on a network must have a unique number on the subnet where it resides in order to identify it in the Controller Tool for uploading down...

Страница 15: ...tions on the input and output terminals including the integrated DPT It assumes all Universal Inputs UIs are Nickel temperature sensors All Configurable Outputs COs are treated as Binary Outputs BOs w...

Страница 16: ...uses to trip make sure that the power connections on theVMA1930 are not reversed The most common cause of this problem is when the 24 VAC power supply on the VMA1930 is reversed but not reversed on a...

Страница 17: ...Transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not shared between multiple pieces of equipment Configurable output analog mode is invalid 0 1...

Страница 18: ...cm 30 in Primary Leads and 76 2 cm 30 in Secondary Leads Class 2 Y65A13 0 Transformer 120 VAC Primary to 24 VAC Secondary 40 VA Foot Mount Y65AS 20 32 cm 8 in Primary Leads and 76 2 cm 30 in Secondar...

Страница 19: ...een 001 and 999 Communications Bus Two Ethernet ports 10 100 Mbps 8 pin RJ 45 connector SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended from the VMA controller for netw...

Страница 20: ...nced Application Controller B AAC based on the ANSI ASHRAE 135 2016 The performance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these sp...

Отзывы: