TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions    

17

 

Troubleshooting 

Table 6: N2 Bus Configuration Troubleshooting 

Error/Trouble 
Condition 

Possible Causes 

Solution 

TEC2103-2 thermostat 
cycles online and 
offline. 

Two or more controllers have the same 
address. 

Change each duplicate address to a unique 
number. 

There are Y or T taps or the repeater lost 
power or is wired incorrectly. 

Refer to the 

N2 Communications Bus Technical 

Bulletin (LIT-636018)

TEC2103-2 thermostat 
does not come online. 

Two or more controllers have the same 
address. 

Change each duplicate address to a unique 
number. 

N2 Bus contains too many devices. 

The maximum of N2 devices allowed on the 
N2 Bus is as follows: 100 devices per NCM, 
32 devices per N30, 32 devices per N31, 
150 devices per the Companion/Facilitator 
system. 

TEC2103-2 thermostat does not have 
power. 

Apply power to the TEC2103-2 thermostat. 

N2 cable runs are broken. 

Locate and correct the wiring. 

Device type is incorrect. 

TEC2103-2 thermostat address must be VND 
device type. 

Entire N2 Bus is offline. 

EOL jumpers on MM-CVT101 or NCM are 
not installed. 

Install EOL jumpers properly. 

MM-CVT101 is not plugged into the 
Personal Computer (PC) or 120 VAC 
source. 

Plug MM-CVT101 into PC or plug it into a 
120 VAC source. 

Wiring near the Bus is broken. 

Repair the wiring. 

No point mapping entered.  

Define the BAS dataset. 

 

Table 7: Alarm Messages 

Display 

Function 

Frost ON 

Indicates heating is energized by the low limit frost protection (42

°

F [5.5

°

C]). 

Service 

Indicates there is a service alarm in accordance with one of the programmable Digital 
Inputs (DI1 or DI2). 

Filter 

Indicates the filter (or filters) are dirty in accordance with one of the programmable 
Digital Inputs (DI1 or DI2). 

Note:

 

There is a temperature alarm message that appears at the headend control should the setpoint not be reached 

within 45 minutes (there is no indication locally at the TEC2103-2 thermostat). 

Содержание TEC2103-2

Страница 1: ...thermostat on a partitioning interior wall and approximately 5 ft 1 5 m above the floor in a location of average temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills stairwells or outside doors away from steam or water pipes warm air stacks unheated uncooled areas or sources of electrical interference To install the thermostat 1 Remove the security scr...

Страница 2: ... que dispositif de contrôle de fonctionnement Lorsqu une défaillance ou un dysfonctionnement du thermostat risque de provoquer des blessures ou d endommager l équipement contrôlé ou un autre équipement la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires Veiller dans ce cas à intégrer de façon permanente d autres dispositifs tels que des systèmes de supe...

Страница 3: ... appropriate terminal according to the TEC2103 2 thermostat wiring diagram Figure 5 2 Gently push excess wire back into the wall plug the wall hole with fireproof material to prevent drafts from affecting ambient temperature readings and install screw terminal blocks back onto the PCB 3 Reattach the thermostat cover to the installed base top side first and install the security screw on the bottom ...

Страница 4: ...or N2 Bus Function Y1 Y2 G RC C RH W1 W2 D1 D2 RS Scom OS N2 N2 REF Terminal OS D2 Scom RS D1 Remote Room Sensor OS REF N2 N2 Auxiliary Outdoor Sensor N2 N2 REF Metasys CPN NCM Cool 2 Figure 5 TEC2103 2 Thermostat Wiring Schematic Connecting the N2 Bus To connect the N2 Bus 1 Observe the polarity when connecting the N2 Bus wires to the TEC2103 2 thermostat Note An End of Line EOL is not needed on ...

Страница 5: ...BI CSBD 0 Off 1 On G State Fan BD 8 N2 BI CSBD 0 Off 1 On Temp Unitsa c Local Display Only BD 9 N2 BO See Footnote c 0 C 1 F Occupancy Override BD 10 N2 BI CSBD 0 No Override 1 Override DI1b f BI 1 N2 BI CSBI 0 Off 1 On Temp Alarmb BI 2 N2 BI CSBI 0 Normal 1 Alarm DI2b f BI 3 N2 BI CSBI 0 Off 1 On Notes a Commandable b Can be a Change of State COS alarm to the BAS or N2 Dialer Module NDM to initia...

Страница 6: ...stablished in the controller by Minimum Heat SP ADI 7 read only and Maximum Heat SP ADI 8 The value for Cooling SP ADI 4 and Setback Cooling SP ADI 6 must stay within the limits established in the controller by Minimum Cool SP ADI 9 and Maximum Cool SP ADI 10 read only If a setpoint is overridden the TEC if necessary adjusts the other setpoint to maintain the minimum 2 F deadband between the setpo...

Страница 7: ... to manually scroll to the next parameter on the menu When left unattended for 45 seconds the display resumes scrolling NO key when you do not desire a parameter change and to advance to the next menu item MENU key to access the Main User Menu or exit the menu UP DOWN arrow keys to adjust values activate a Temporary Setpoint Configuration Key T600_TEC_Config_Key Figure 7 Configuration Key Location...

Страница 8: ...ving the front cover and pressing the configuration key Figure 7 Exit the Installer Configuration Menu any time by pressing the MENU key and at the exit prompt pressing the YES key To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds it reverts to the Status Display Menu Table 2 Installer Configu...

Страница 9: ... Status Display Menu and when the message is displayed the backlight momentarily lights up Each digital input can be programmed in one of four conditions None No function is associated with the input Service A Service alarm is displayed Filter A Filter alarm is displayed RemOVR Remote Override OVR contact This disables all override menu functions of the thermostat The override function is now cont...

Страница 10: ... for instructions Enabling Frost Protection Frost pr Frost protection establishes a minimum heating setpoint of 42 F 5 5 C to prevent freezing in the zone controlled by the thermostat If enabled frost protection is activated even if the thermostat is set to the Off System Mode If frost protection is active it is displayed as an alarm Frost on with the backlight lit on the Status Display Menu To en...

Страница 11: ...m Heating Stage Cycles per Hour Heat cph section for instructions Setting the Maximum Heating Stage Cycles per Hour Heat cph The heating cycles per hour establishes the maximum number of times the equipment or stages are turned on and off in one hour The selection ranges from three to eight cycles per hour Note A higher number of heating cycles per hour results in more accurate temperature control...

Страница 12: ...ting the N2 Address N2 addr To adjust the N2 address adjustable from 1 to 253 while in the Installer Configuration Menu 1 Answer NO to all prompts until the setting the N2 address prompt appears in the display Press YES to set the address 2 Use the UP DOWN arrow keys to display the desired address Press YES to store the address The display now shows the temporary occupancy time prompt See the Esta...

Страница 13: ...w keys select 1 0 or 2 0 stages Press YES to store the selection The display now shows the heating lockout prompt See the Setting the Heating Lockout H lock section for instructions Setting the Heating Lockout H lock This feature disables heating operation based on auxiliary or outdoor air temperature requires temperature sensor to be connected to the Auxiliary Outdoor Air Sensor terminal OS for t...

Страница 14: ...the first prompt 2 Press YES to enable the temporary override The TEC2103 2 thermostat returns to the Status Display Menu When scrolling through the Status Display Menu Override now appears for the schedule status parameter Resuming the Programmed Schedule only appears when in the Override Mode To resume the schedule while in the Main User Menu 1 Answer NO to all prompts until the Resume Schedule ...

Страница 15: ...he temporary setpoint for the current mode of operation Note Whether the thermostat is heating or cooling the respective setpoint will be temporarily adjusted Note To toggle between the temporary heating and cooling setpoints press the NO key while changing the temporary setpoints Note If a setpoint is overridden over the N2 network it appears the setpoint value can be changed through the TEC2103 ...

Страница 16: ...upied and unoccupied periods even if the system mode is set to off Automatic Fan Mode auto Operates the fan only on a call for heating or cooling for both occupied and unoccupied periods Smart Fan Mode smart Energizes the fan all the time for occupied periods and only on a call for heating and cooling in unoccupied periods This is the default setting To set the fan mode while in the Main User Menu...

Страница 17: ...pply power to the TEC2103 2 thermostat N2 cable runs are broken Locate and correct the wiring Device type is incorrect TEC2103 2 thermostat address must be VND device type Entire N2 Bus is offline EOL jumpers on MM CVT101 or NCM are not installed Install EOL jumpers properly MM CVT101 is not plugged into the Personal Computer PC or 120 VAC source Plug MM CVT101 into PC or plug it into a 120 VAC so...

Страница 18: ...6 x 29 mm Shipping Weight 0 75 lb 0 34 kg UL and cUL Listing File E27734 with CCN s XAPX US UL 873 and XAPX7 Canada CSA C22 2 No 24 FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interference when this eq...

Страница 19: ... GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA Building Efficiency 507 E Michigan Street Milwaukee WI 53202 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2016 Johnson Contr...

Отзывы: