TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions
11
To set the minimum cooling setpoint while in the
Installer Configuration Menu:
1. Answer NO to all prompts until the minimum
cooling setpoint prompt appears in the display.
Press YES to enter the minimum cooling setpoint
menu.
2. Use the UP/DOWN arrow keys to adjust the
minimum cooling setpoint temperature. Press YES
to store the value.
The display now shows the anti-short cycle timer
prompt. See the
Setting the Anti-Short Cycle Timer
(Anticycl)
section for instructions.
Setting the Anti-Short Cycle Timer (Anticycl)
The anti-short cycle timer establishes the minimum
on/off times for the cooling and heating stages. The
timer is adjustable from 0 to 5 minutes in 1-minute
increments. Set the anti-short cycling to 0 minutes for
equipment that possesses its own anti-short cycling
timer.
!
CAUTION: Risk of Property Damage.
Do not set the TEC2103-2 thermostat’s
anti-short
cycling timer to 0 minutes if the controlled equipment
is not protected by its own internal anti-short cycling
timer. Setting the anti-short cycling timer to 0
minutes may result in damage to the controller.
MISE EN GARDE : Risque de dégâts matériels.
Ne pas régler le temporisateur anti court-cycle de l'
TEC2103-2 thermostat sur 0 minute si l'équipement
contrôlé n'est pas protégé par son propre
temporisateur anti court-cycle interne. Le réglage du
temporisateur anti court-cycle sur 0 minute risque
d'endommager le régulateur.
To set the anti-short cycle time while in the Installer
Configuration Menu:
1. Answer NO to all prompts until the anti-short cycle
timer prompt appears in the display. Press YES to
enter the anti-short cycling timer menu.
2. Use the UP/DOWN arrow keys to adjust the
minimum on/off times for the heating and cooling
stages. Press YES to store the value.
The display now shows the heating cycles per hour
setup prompt. See the
Setting the Maximum Heating
Stage Cycles per Hour (Heat cph)
section for
instructions.
Setting the Maximum Heating Stage Cycles per
Hour (Heat cph)
The heating cycles per hour establishes the maximum
number of times the equipment or stages are turned
on and off in one hour. The selection ranges from
three to eight cycles per hour.
Note:
A higher number of heating cycles per hour
results in more accurate temperature control but could
accelerate the wear of mechanical components in the
equipment.
To set the maximum number of heating cycles per
hour while in the Installer Configuration Menu:
1. Answer NO to all prompts until the heating cycles
per hour prompt appears in the display. Press
YES to enter the heating cycles per hour menu.
2. Use the UP/DOWN arrow keys to adjust the
maximum number of heating cycles per hour.
Press YES to store the value.
The display now shows the cooling cycles per hour
setup prompt. See the
Setting the Maximum Cooling
Stage Cycles per Hour (Cool cph)
section for
instructions.
Setting the Maximum Cooling Stage Cycles per
Hour (Cool cph)
The cooling cycles per hour establishes the maximum
number of times the equipment or stages are turned
on and off in one hour. The selection ranges from
three to four cycles per hour.
Note:
A higher number of cooling cycles per hour
results in more accurate temperature control but could
accelerate the wear of mechanical components in the
equipment.
To set the maximum number of cooling cycles per
hour while in the Installer Configuration Menu:
1. Answer NO to all prompts until the cooling cycles
per hour prompt appears in the display. Press
YES to enter the cooling cycles per hour menu.
2. Use the UP/DOWN arrow keys to adjust the
maximum number of cooling cycles per hour.
Press YES to store the value.
The display now shows the minimum heating/cooling
deadband prompt. See the
Setting the
Heating/Cooling Deadband (Deadband)
section for
instructions.
Setting the Heating/Cooling Deadband (Deadband)
The heating/cooling deadband setting establishes the
minimum difference between the heating and cooling
setpoints. The range is adjustable from 2 to 4 F
°
(1 to 2 C
°
).