background image

 

8    

TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions 

Programming Overview 

There are three menus used to view, program, and 
configure the TEC2103-2 thermostat: Status Display, 
Main User, and Installer Configuration Menus. 

The 

Status Display Menu

 displays during normal 

thermostat operation. The menu continually scrolls 
through the following parameters. 

 

Room Temperature 

 

System Mode 

 

Schedule Status (Occupied/Unoccupied/Override) 

Note: 

Override displays only when in the Override 

mode. 

 

Auxiliary Temperature (Displays outdoor or other 
auxiliary temperatures. Requires the sensor to be 
wired to the Auxiliary/Outdoor Air Sensor terminal 
OS [Figure 5]). The maximum temperature 
displayed is 122

°

F (50

°

C). The actual temperature 

may be above this point. 

 

Applicable Alarms (the backlight lights up as an 
alarm condition is displayed) 

To temporarily stop the scrolling, press the 
YES/SCROLL key. 

Use the 

Main User Menu

 to access and change the 

thermostat’s basic operating parameters. Access the 
menu by pressing the MENU key during normal 
thermostat operation. 

Use the 

Installer Configuration Menu

 to set up the 

thermostat for application specific operation. Access 
the menu by removing the front cover and pressing the 
configuration key, labeled CONFIG (Figure 7). 

Configuring the TEC2103-2 thermostat 

The TEC2103-2 thermostat ships from the factory with 
default settings for all configurable parameters. The 
default settings are shown in Table 2. To reconfigure 
the parameters, follow the steps in this section for the 
corresponding parameters. The parameters must be 
set up first by accessing the Installer Configuration 
Menu. Access the Installer Configuration Menu by 
removing the front cover and pressing the 
configuration key (Figure 7). 

Exit the Installer Configuration Menu any time by 
pressing the MENU key and, at the exit prompt, 
pressing the YES key. To pass over a parameter 
without changing it press the NO key. 

When the thermostat is in the Installer Configuration 
Menu and left unattended for 45 seconds, it reverts to 
the Status Display Menu. 

Table 2: Installer Configuration Menu 

 

Remove the cover and press the 

CONFIG key from the Status Display 

Menu to enter the Installer 
Configuration Menu. 

 

Configures Digital Input 1 
Default: No Function 

(None) 

See the 

Configuring the Digital Inputs 

(DI1 and DI2) 

section

.

 

 

Configures Digital Input 2 
Default: No Function 

(None) 

See the 

Configuring the Digital Inputs 

(DI1 and DI2) 

section. 

 

Sets Keypad Lockout Level 
Default: No Lockout 

(0) 

See the 

Enabling the Keypad Lockout 

(Lockout) 

section

.

 

 

Sets Power-up Delay 
Default: Ten Seconds 

(10.0 sec) 

See the 

Setting the Power-Up Delay 

(Pwr del) 

section

.

 

 

Enables/Disables Frost Protection 
Default: Disabled 

(Off) 

See the 

Enabling Frost Protection 

(Frost pr) 

section

.

 

 

Sets the Maximum Heating Setpoint 
Default: 

90.0

°

F (32.0

°

C)

 

See the 

Setting the Maximum Heating 

Setpoint (Heat max) 

section

.

 

 

Sets the Minimum Cooling Setpoint 
Default: 

54.0

°

F (12.0

°

C)

 

See the 

Setting the Minimum Cooling 

Setpoint (Cool min) 

section

.

 

 

Sets the Anti-Short Cycle Timer 
Default: Two Minutes 

(2.0 min)

 

See the 

Setting the Anti-Short Cycle 

Timer (Anticycl) 

section

.

 

 

Sets the Heating Cycles per Hour 
Default: Four 

(4.0) 

See the 

Setting the Maximum Heating 

Stage Cycles per Hour (Heat cph) 

section

.

 

 

Sets the Cooling Cycles per Hour 
Default: Four 

(4.0) 

See the 

Setting the Maximum Cooling 

Stage Cycles per Hour (Cool cph) 

section

.

 

Continued on next page . . . 

RoomTemp 
75.0 

°

F

 

DI1 
set? Y/N

 

 

DI2 
set? Y/N 

Lockout 
set? Y/N 

Pwr del 
set? Y/N 

Frost pr 
set? Y/N 

Heat max 
set? Y/N 

Cool min 
set? Y/N 

Cool cph 
set? Y/N 

Heat cph 
set? Y/N 

Anticycl 
set? Y/N 

Содержание TEC2103-2

Страница 1: ...thermostat on a partitioning interior wall and approximately 5 ft 1 5 m above the floor in a location of average temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills stairwells or outside doors away from steam or water pipes warm air stacks unheated uncooled areas or sources of electrical interference To install the thermostat 1 Remove the security scr...

Страница 2: ... que dispositif de contrôle de fonctionnement Lorsqu une défaillance ou un dysfonctionnement du thermostat risque de provoquer des blessures ou d endommager l équipement contrôlé ou un autre équipement la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires Veiller dans ce cas à intégrer de façon permanente d autres dispositifs tels que des systèmes de supe...

Страница 3: ... appropriate terminal according to the TEC2103 2 thermostat wiring diagram Figure 5 2 Gently push excess wire back into the wall plug the wall hole with fireproof material to prevent drafts from affecting ambient temperature readings and install screw terminal blocks back onto the PCB 3 Reattach the thermostat cover to the installed base top side first and install the security screw on the bottom ...

Страница 4: ...or N2 Bus Function Y1 Y2 G RC C RH W1 W2 D1 D2 RS Scom OS N2 N2 REF Terminal OS D2 Scom RS D1 Remote Room Sensor OS REF N2 N2 Auxiliary Outdoor Sensor N2 N2 REF Metasys CPN NCM Cool 2 Figure 5 TEC2103 2 Thermostat Wiring Schematic Connecting the N2 Bus To connect the N2 Bus 1 Observe the polarity when connecting the N2 Bus wires to the TEC2103 2 thermostat Note An End of Line EOL is not needed on ...

Страница 5: ...BI CSBD 0 Off 1 On G State Fan BD 8 N2 BI CSBD 0 Off 1 On Temp Unitsa c Local Display Only BD 9 N2 BO See Footnote c 0 C 1 F Occupancy Override BD 10 N2 BI CSBD 0 No Override 1 Override DI1b f BI 1 N2 BI CSBI 0 Off 1 On Temp Alarmb BI 2 N2 BI CSBI 0 Normal 1 Alarm DI2b f BI 3 N2 BI CSBI 0 Off 1 On Notes a Commandable b Can be a Change of State COS alarm to the BAS or N2 Dialer Module NDM to initia...

Страница 6: ...stablished in the controller by Minimum Heat SP ADI 7 read only and Maximum Heat SP ADI 8 The value for Cooling SP ADI 4 and Setback Cooling SP ADI 6 must stay within the limits established in the controller by Minimum Cool SP ADI 9 and Maximum Cool SP ADI 10 read only If a setpoint is overridden the TEC if necessary adjusts the other setpoint to maintain the minimum 2 F deadband between the setpo...

Страница 7: ... to manually scroll to the next parameter on the menu When left unattended for 45 seconds the display resumes scrolling NO key when you do not desire a parameter change and to advance to the next menu item MENU key to access the Main User Menu or exit the menu UP DOWN arrow keys to adjust values activate a Temporary Setpoint Configuration Key T600_TEC_Config_Key Figure 7 Configuration Key Location...

Страница 8: ...ving the front cover and pressing the configuration key Figure 7 Exit the Installer Configuration Menu any time by pressing the MENU key and at the exit prompt pressing the YES key To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds it reverts to the Status Display Menu Table 2 Installer Configu...

Страница 9: ... Status Display Menu and when the message is displayed the backlight momentarily lights up Each digital input can be programmed in one of four conditions None No function is associated with the input Service A Service alarm is displayed Filter A Filter alarm is displayed RemOVR Remote Override OVR contact This disables all override menu functions of the thermostat The override function is now cont...

Страница 10: ... for instructions Enabling Frost Protection Frost pr Frost protection establishes a minimum heating setpoint of 42 F 5 5 C to prevent freezing in the zone controlled by the thermostat If enabled frost protection is activated even if the thermostat is set to the Off System Mode If frost protection is active it is displayed as an alarm Frost on with the backlight lit on the Status Display Menu To en...

Страница 11: ...m Heating Stage Cycles per Hour Heat cph section for instructions Setting the Maximum Heating Stage Cycles per Hour Heat cph The heating cycles per hour establishes the maximum number of times the equipment or stages are turned on and off in one hour The selection ranges from three to eight cycles per hour Note A higher number of heating cycles per hour results in more accurate temperature control...

Страница 12: ...ting the N2 Address N2 addr To adjust the N2 address adjustable from 1 to 253 while in the Installer Configuration Menu 1 Answer NO to all prompts until the setting the N2 address prompt appears in the display Press YES to set the address 2 Use the UP DOWN arrow keys to display the desired address Press YES to store the address The display now shows the temporary occupancy time prompt See the Esta...

Страница 13: ...w keys select 1 0 or 2 0 stages Press YES to store the selection The display now shows the heating lockout prompt See the Setting the Heating Lockout H lock section for instructions Setting the Heating Lockout H lock This feature disables heating operation based on auxiliary or outdoor air temperature requires temperature sensor to be connected to the Auxiliary Outdoor Air Sensor terminal OS for t...

Страница 14: ...the first prompt 2 Press YES to enable the temporary override The TEC2103 2 thermostat returns to the Status Display Menu When scrolling through the Status Display Menu Override now appears for the schedule status parameter Resuming the Programmed Schedule only appears when in the Override Mode To resume the schedule while in the Main User Menu 1 Answer NO to all prompts until the Resume Schedule ...

Страница 15: ...he temporary setpoint for the current mode of operation Note Whether the thermostat is heating or cooling the respective setpoint will be temporarily adjusted Note To toggle between the temporary heating and cooling setpoints press the NO key while changing the temporary setpoints Note If a setpoint is overridden over the N2 network it appears the setpoint value can be changed through the TEC2103 ...

Страница 16: ...upied and unoccupied periods even if the system mode is set to off Automatic Fan Mode auto Operates the fan only on a call for heating or cooling for both occupied and unoccupied periods Smart Fan Mode smart Energizes the fan all the time for occupied periods and only on a call for heating and cooling in unoccupied periods This is the default setting To set the fan mode while in the Main User Menu...

Страница 17: ...pply power to the TEC2103 2 thermostat N2 cable runs are broken Locate and correct the wiring Device type is incorrect TEC2103 2 thermostat address must be VND device type Entire N2 Bus is offline EOL jumpers on MM CVT101 or NCM are not installed Install EOL jumpers properly MM CVT101 is not plugged into the Personal Computer PC or 120 VAC source Plug MM CVT101 into PC or plug it into a 120 VAC so...

Страница 18: ...6 x 29 mm Shipping Weight 0 75 lb 0 34 kg UL and cUL Listing File E27734 with CCN s XAPX US UL 873 and XAPX7 Canada CSA C22 2 No 24 FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interference when this eq...

Страница 19: ... GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA Building Efficiency 507 E Michigan Street Milwaukee WI 53202 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2016 Johnson Contr...

Отзывы: