TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions
9
Table 2: Installer Configuration Menu (Cont.)
Sets the Minimum Heating/Cooling
Deadband
Default:
2.0
°
F (1.1
°
C)
See the
Setting the Heating/Cooling
Deadband (Deadband)
section
.
Determines how the Fan Activates in
Response to a call for Heat
Default: Thermostat Controls Fan
(On)
See the
Setting the Fan Control
(Fan cont)
section
.
Delays Fan Termination at Cycle’s End
for 60 Seconds
Default: No Delay
(Off)
See the
Setting the Fan Delay
(Fan del)
section
.
Sets the N2 Address
Default:
253
See the
Setting the N2 Address
(N2 addr)
section
.
Sets the Duration for Temporary
Occupancy Time
Default: Three Hours
(3.0 hrs)
See the
Establishing the Temporary
Occupancy Time (TOccTime)
section
.
Room Air Sensor Calibration (Offset)
Default:
0.0
°
F (0.0
°
C)
See the
Room Air Sensor Calibration
(Cal RS)
section
.
Auxiliary/Outdoor Air Sensor
Calibration (Offset)
Default:
0.0
°
F (0.0
°
C)
See the
Auxiliary
Temperature/Outdoor Air Sensor
Calibration (Cal OS)
section
.
Disable/Enable Second Heating Stage
Default:
Two Stages
See the
Disable/Enable Second
Heating Stage (H Stage)
section
.
Disable/Enable Second Cooling Stage
Default:
Two Stages
See the
Disable/Enable Second
Cooling Stage (C Stage)
section
.
Disables Heating Operation based on
Auxiliary/Outdoor Air Temperature
Default:
123
°
F (51
°
C)
See the
Setting the Heating Lockout
(H lock)
section
.
Disables Cooling Operation based on
Outdoor Air Temperature
Default:
-40
°
F (-40
°
C)
See the
Setting the Cooling Lockout
(C lock)
section
.
Configuring the Digital Inputs (DI1 and DI2)
Press the configuration menu access key. The first
prompt is to program Digital Inputs DI1 and DI2.
The digital inputs display an alarm condition when the
input is closed. An alarm message is included on the
scrolling Status Display Menu and when the message
is displayed, the backlight momentarily lights up.
Each digital input can be programmed in one of four
conditions.
•
None
– No function is associated with the input.
•
Service
– A Service alarm is displayed.
•
Filter
– A Filter alarm is displayed.
•
RemOVR
– Remote Override (OVR) contact. This
disables all override menu functions of the
thermostat. The override function is now controlled
manually by a remote, momentarily closed
contact. When configured in this mode, the input
operates in a toggle mode. With this function
enabled, it is now possible to toggle between
unoccupied and occupied setpoints for the amount
of time set by the temporary occupancy time
parameter.
When override is enabled through the digital
inputs, an
Override
message appears in the
Status Display Menu.
To configure the digital inputs while in the Installer
Configuration Menu:
1. Press YES to configure Digital Input 1 or NO to
advance to Digital Input 2.
2. Use the UP/DOWN arrow keys to locate the
desired function for the Digital Input 1. Press YES
to select the desired function.
3. Press YES to configure Digital Input 2 or NO to
advance to the keypad lockout setup prompt.
4. Use the UP/DOWN arrow keys to locate the
desired function for the Digital Input 2. Press YES
to select the desired function.
The display now shows the keypad lockout setup
prompt. See the
Enabling the Keypad Lockout
(Lockout)
section for instructions.
Note:
Regardless of the digital input configuration
(
None
,
Service
,
Filter or RemOVR
) established
through the local interface at the TEC2103-2
thermostat, the states of DI1 and DI2 are
communicated over the N2 network. This enables the
ability to communicate alarm conditions over the
network without local annunciation on the TEC2103-2
thermostat display.
Deadband
set? Y/N
Fan cont
set? Y/N
TOccTime
set? Y/N
Cal RS
set? Y/N
Cal OS
set? Y/N
H lock
set? Y/N
C lock
set? Y/N
Fan del
set? Y/N
N2 addr
set? Y/N
H Stage
set? Y/N
C Stage
set? Y/N